| 2004-11-12 00:00:00 | *********** UNSAT ********** |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE:PLEASE VERIFY SIZE OF HEAT |
| | SHOWN, |
| | SHOWS 8KW. PLEASE SEE THIS MAY BE |
| | UNDER-SIZED FOR SQ FT OF DWELLING. |
| | |
| | 3)NOTE: PLEASE SEE FBC CHAPTER 34 |
| | 3401.7.1.2.1/ 3401.7.2.6 FOR ADDITIONS |
| | AND REMODELS OF EXISTING DWELLINGS. |
| | PLEASE SHOW EXSITNG ELECTRICAL TO MEET |
| | 2002 NEC . |
| | PLEASE SHOW EITHER ALL NEW OR EXSITNG |
| | SD'S WHICH ARE REQUIRED TO MEET NFPA-72 |
| | 8-1.4.1.6.2 |
| | |
| | |
| | 4)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |