Plan Review Notes
Plan Review Notes For Permit 04101253
Permit Number 04101253
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-12 00:00:00*********** UNSAT **********
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE:PLEASE VERIFY SIZE OF HEAT
 SHOWN,
 SHOWS 8KW. PLEASE SEE THIS MAY BE
 UNDER-SIZED FOR SQ FT OF DWELLING.
  
 3)NOTE: PLEASE SEE FBC CHAPTER 34
 3401.7.1.2.1/ 3401.7.2.6 FOR ADDITIONS
 AND REMODELS OF EXISTING DWELLINGS.
 PLEASE SHOW EXSITNG ELECTRICAL TO MEET
 2002 NEC .
 PLEASE SHOW EITHER ALL NEW OR EXSITNG
 SD'S WHICH ARE REQUIRED TO MEET NFPA-72
 8-1.4.1.6.2
  
  
 4)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.