| 2005-01-31 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FBC 104.2.1, ALL |
| | PLANS ARE REQUIRED TO HAVE THE PRINTED |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS/DESIGN. |
| | PLEASE ALSO SEE ARCH SHEETS WHICH ARE |
| | STILL MISSING REQUIRED TITLE BLOCKS AS |
| | NOTED ON PREVIOUS REVIEW. |
| | FAC 61G1-16.004, FS 481 |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | |
| | 2)NOTE: PLEASE SHOW ALL RECEPTS |
| | SERVING KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECTED PER 210.8A-6 |
| | |
| | 3)NOTE: PLEASE SEE MISSING SD LEADING TO |
| | FLR ABOVE. PER NFPA-72 8-1.4.1.6.2 |
| | |
| | 4)NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING PER 210.70 |
| | DOORS WITH GRADE LEVEL ACCESS. |
| | |
| | 5)NOTE: PLEASE SEE MISSING GFI FOR COND |
| | UNITS. 210.63 |
| | |
| | 6)NOTE: PLEASE SEE MIN OCP FOR AHU'S PER |
| | 424.3B MIN 125% |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.52 |
| | |
| | 8)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON PLANS. |
| | |
| | PLEASE SEE MOST OF THE ABOVE ITEMS ARE |
| | REDLINED ON PLANS SUBMITTED FOR |
| | REFERENCE OF ABOVE NOTES. |
| | |
| | PLEASE REMOVE ALL OLD VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| | FOR ALL TRADES. |
| | PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR |
| | REFERENCE. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |