| Plan Review Notes For Permit 04101222 |
| Permit Number |
04101222 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-15 00:00:00 | DENIED | | | | | | 1) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND HAVE DOCUMENT | | | ATTESTING TO THIS CERTIFICATION PRIOR | | | TO FINAL APPROVAL OF THE FIRE ALARM | | | SYSTEM. | | | | | | 2) WEST PALM BEACH FIRE MARSHAL OFFICE | | | REQUIRES DUCT DETECTORS TO SEND A | | | "ALARM" CONDITION, NOT A "SUPERVISORY". | | | | | | 3) THE FIRE ALARM SYSTEM SHALL BE CLASS | | | "A" OR FULLY ADDRESSABLE. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|