| 2005-01-10 00:00:00 | DENIED |
| | |
| | 1) SUBMIT THE STATE PRODUCT APPROVAL FOR |
| | THE 16'X 8' (4) PANEL SLIDING GLASS |
| | DOOR. THE ONE SUBMITTED IS FOR A THREE |
| | PANEL DOOR. |
| | |
| | 2) THE PRODUCT APPROVALS SUBMITTED FOR |
| | THE WINDOW MULLIONS ARE LIMITED IN SIZE |
| | AND WILL NOT WORK IN THE TWO LARGE |
| | OPENINGS AT THE LIVING ROOM AND MASTER |
| | BEDROOM. SUBMIT THE APPROPRIATE PROD. |
| | APPROVALS. |
| | |
| | 3) THE PRODUCT APPROVAL DRAWINGS FOR THE |
| | 9' AND 16' WIDE GARAGE DOORS HAVE DESIGN |
| | PRESSURES LOWER THAN THE REQUIRED |
| | PRESSURES LISTED ON THE PLANS. |
| | |
| | 4) SUBMIT TWO COPIES OF THE PRODUCT |
| | APPROVAL, KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. THE |
| | FLORIDA PRODUCT APPROVAL THAT WAS |
| | SUBMITTED IS FOR WEATHER GUARD, INC. AND |
| | THE ATTACHED INFORMATION IS FOR |
| | WEATHERGUARD. THESE ARE TWO DIFFERENT |
| | COMPANIES. |
| | |
| | 5) THE GLAZING PRODUCTS SUBMITTED WITH |
| | AAMA CERTIFICATION HAVE NOT BEEN TESTED |
| | FOR LARGE MISSLE IMPACT AND ARE REQUIRED |
| | TO BE PROTECTED WITH STORM PANELS. |
| | |
| | 6) THE ID MARK (F-) IN THE FOOTING |
| | SCHEDULE SHOULD BE (F-10). PLEASE |
| | CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |