| Plan Review Notes For Permit 04101196 |
| Permit Number |
04101196 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A-4 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. THE RISER | | | DIAGRAM SHOWS TWO SHOWERS IN BATH #2, | | | BUT THE FLOOR PLAN SHOWS ONLY ONE. THE | | | TUB IN BATH #3 IS ON THE RIGHT SIDE OF | | | THE W/C ON THE FLOOR PLAN, BUT IS SHOWN | | | NEAR THE LAV ON THE RISER DIAGRAM. SHOW | | | ALL PIPE SIZES ON THE RISER DIAGRAM, | | | MANY SECTIONS IN THE MASTER BATH DO NOT | | | HAVE PIPE SIZES. SECTION 104.2.1. | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|