| 2004-11-12 00:00:00 | ********** UNSAT *************** |
| | |
| | |
| | 1 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | PLANS ONLY REFLECT RECEPTS. |
| | |
| | 2)NOTE: PLEASE SEE MISSING SD'S INSIDE |
| | AND OUTSIDE LIB/BEDRM. THIS RM WHICH |
| | CONTAINS A CLOSET IS CONSIDEREDTO BE |
| | AN ADAPTABLE BEDRM. |
| | PLEASE ALSO SEE LOCATION OF SD IN |
| | MASTER |
| | BEDRM SUITE, PLANS SHOWS TWO SD'S IN |
| | BEDRM? NONE OUTSIDE. |
| | NFPA-72 8-1.4.1.6.2 |
| | PLEASE SEE 8-1.4.2 FOR SD LOCATIONS, |
| | 3' MIN AWAY FROM BATHS. |
| | |
| | 3)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING, 2' OF WALL SPACING. |
| | |
| | 4)NOTE: PLEASE SEE MISSING GFI RECEPT IN |
| | MECH RM. 210.63 |
| | PLEASE ALSO SEEGFI FOR COND UNIT. |
| | |
| | 5)NOTE: PLEASE SEE MISSING EGRESS LT |
| | REQUIRED FROM CABANA BATH TO OUTSIDE. |
| | 210.70 |
| | |
| | |
| | PLEASE SEE ONE SET OF PLANS HAS SOME OF |
| | THE ABOVE ITEMS REDLINED ON PLANS. |
| | |
| | PLEASE REMOVE ALLOLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |