2004-11-12 00:00:00********** UNSAT ***************
  
  
 1 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 PLANS ONLY REFLECT RECEPTS.
  
 2)NOTE: PLEASE SEE MISSING SD'S INSIDE
 AND OUTSIDE LIB/BEDRM. THIS RM WHICH
 CONTAINS A CLOSET IS CONSIDEREDTO BE
 AN ADAPTABLE BEDRM.
 PLEASE ALSO SEE LOCATION OF SD IN
 MASTER
 BEDRM SUITE, PLANS SHOWS TWO SD'S IN
 BEDRM? NONE OUTSIDE.
 NFPA-72 8-1.4.1.6.2
 PLEASE SEE 8-1.4.2 FOR SD LOCATIONS,
 3' MIN AWAY FROM BATHS.
  
 3)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING, 2' OF WALL SPACING.
  
 4)NOTE: PLEASE SEE MISSING GFI RECEPT IN
 MECH RM. 210.63
 PLEASE ALSO SEEGFI FOR COND UNIT.
  
 5)NOTE: PLEASE SEE MISSING EGRESS LT
 REQUIRED FROM CABANA BATH TO OUTSIDE.
 210.70
  
  
 PLEASE SEE ONE SET OF PLANS HAS SOME OF
 THE ABOVE ITEMS REDLINED ON PLANS.
  
 PLEASE REMOVE ALLOLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]