Plan Review Notes
Plan Review Notes For Permit 04101196
Permit Number 04101196
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-02 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. SEE FBC TABLE 1604.1 FOR
 REQUIREMENTS.
  
 3) THE FOOTING SCHEDULE ON A1 IS MISSING
 THE F-10 MARK.
  
 4) ON SHEET A2 SPECIFY SAFETY GLAZING
 FOR THE WINDOWS AT THE BATH TUB IN THE
 LADIES SUITE AND BESIDE THE SHOWER IN
 HIS BATH.
  
 5) A DETAIL 5/A5 IS SPECIFIED ON THE
 PLANS ON A5 AND A6, BUT THE DETAIL IS
 NOT GIVEN.
  
 6) SEVERAL OF THE DETAILS CALLED OUT IN
 THE ROOF PLAN ON A6 DO NOT CORRESPOND
 WITH THE DETAILS SPECIFIED ON A5. SEE
 MARKS ON THE PLANS.
  
 7) PLEASE CLARIFY THE CONNECTION FOR THE
 THREE GIRDERS THAT MEET AT THE STEEL
 COLUMN SHOWN IN DETAIL 9 ON A5. THE
 BOTTOM OF TWO GIRDERS ARE AT 14' AND THE
 BOTTOM OF THE THIRD IS 10'.
  
 8) THE ENERGY CALCULATION FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER/AGENT PER FBC CHAPTER 13.
  
 9)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) ALL PRODUCT APPROVAL INFORMATION
 SUBMITTED MUST BE CLEAR AND LEGIBLE.
 WHEN MULTIPLE PRODUCTS OR MODELS ARE
 LISTED IN A SINGLE PRODUCT APPROVAL THE
 ONES THAT ARE BEING USED MUST BE
 SPECIFIED AND THE INSTALLATION DRAWINGS
 AND DESIGN PRESSURES FOR THOSE ITEMS
 MUST BE SUBMITTED.
  
 11) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE ARCHED TOP FIXED GLASS WINDOWS
 AND THE STRUCTURAL MULLIONS.
  
 12) SUBMIT AN ACCURATE KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS, LISTING ONLY THE OPENINGS THAT
 WILL BE SHUTTERED. THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR IMPACT
 WINDOWS, WHICH INDICATES THAT ONLY THE
 GLAZED DOORS WOULD BE SHUTTERED.
  
 IF YOU HAVE QUESTIONS PLEASE CALL;
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714