| 2004-12-02 00:00:00 | DENIED |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON |
| | THE PLANS. SEE FBC TABLE 1604.1 FOR |
| | REQUIREMENTS. |
| | |
| | 3) THE FOOTING SCHEDULE ON A1 IS MISSING |
| | THE F-10 MARK. |
| | |
| | 4) ON SHEET A2 SPECIFY SAFETY GLAZING |
| | FOR THE WINDOWS AT THE BATH TUB IN THE |
| | LADIES SUITE AND BESIDE THE SHOWER IN |
| | HIS BATH. |
| | |
| | 5) A DETAIL 5/A5 IS SPECIFIED ON THE |
| | PLANS ON A5 AND A6, BUT THE DETAIL IS |
| | NOT GIVEN. |
| | |
| | 6) SEVERAL OF THE DETAILS CALLED OUT IN |
| | THE ROOF PLAN ON A6 DO NOT CORRESPOND |
| | WITH THE DETAILS SPECIFIED ON A5. SEE |
| | MARKS ON THE PLANS. |
| | |
| | 7) PLEASE CLARIFY THE CONNECTION FOR THE |
| | THREE GIRDERS THAT MEET AT THE STEEL |
| | COLUMN SHOWN IN DETAIL 9 ON A5. THE |
| | BOTTOM OF TWO GIRDERS ARE AT 14' AND THE |
| | BOTTOM OF THE THIRD IS 10'. |
| | |
| | 8) THE ENERGY CALCULATION FORM IS |
| | REQUIRED TO BE SIGNED AND DATED BY THE |
| | OWNER/AGENT PER FBC CHAPTER 13. |
| | |
| | 9)PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 10) ALL PRODUCT APPROVAL INFORMATION |
| | SUBMITTED MUST BE CLEAR AND LEGIBLE. |
| | WHEN MULTIPLE PRODUCTS OR MODELS ARE |
| | LISTED IN A SINGLE PRODUCT APPROVAL THE |
| | ONES THAT ARE BEING USED MUST BE |
| | SPECIFIED AND THE INSTALLATION DRAWINGS |
| | AND DESIGN PRESSURES FOR THOSE ITEMS |
| | MUST BE SUBMITTED. |
| | |
| | 11) SUBMIT STATE/LOCAL PRODUCT APPROVALS |
| | FOR THE ARCHED TOP FIXED GLASS WINDOWS |
| | AND THE STRUCTURAL MULLIONS. |
| | |
| | 12) SUBMIT AN ACCURATE KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS, LISTING ONLY THE OPENINGS THAT |
| | WILL BE SHUTTERED. THE PRODUCT APPROVALS |
| | THAT WERE SUBMITTED ARE FOR IMPACT |
| | WINDOWS, WHICH INDICATES THAT ONLY THE |
| | GLAZED DOORS WOULD BE SHUTTERED. |
| | |
| | IF YOU HAVE QUESTIONS PLEASE CALL; |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |