Plan Review Notes
Plan Review Notes For Permit 04101185
Permit Number 04101185
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-12 00:00:00****** UNSAT ********
  
 1)NOTE: PLEASE SHOW LOCATION OF POOL
 PANEL ON PLANS.
 PLEASE INCLUDE LOAD CALCULATION ON POOL
 PANEL.
 PLEASE SEE CONTINUOUS LOADS TO BE SHOWN
 ON SUB PANEL.
 215.5,215.3,230.42,680.9
  
 2)NOTE: PLEASE SEE THERE ARE MANY
 DEDICATED ITEMS LISTED ONPANEL
 SCHEDULE WHICH ISD NOT SHOWN IN LOAD
 CALCULATIONS,
 PLEASE SEE OVEN, COOKTOP? GARAGE DR
 OPENER,SPA TUB , BBQ FRIG, ETC.
 215.5,220.31
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]