| Notes |
| Date |
Text |
| 2005-08-12 00:00:00 | ****** UNSAT ******** | | | | | | 1)NOTE: PLEASE SHOW LOCATION OF POOL | | | PANEL ON PLANS. | | | PLEASE INCLUDE LOAD CALCULATION ON POOL | | | PANEL. | | | PLEASE SEE CONTINUOUS LOADS TO BE SHOWN | | | ON SUB PANEL. | | | 215.5,215.3,230.42,680.9 | | | | | | 2)NOTE: PLEASE SEE THERE ARE MANY | | | DEDICATED ITEMS LISTED ONPANEL | | | SCHEDULE WHICH ISD NOT SHOWN IN LOAD | | | CALCULATIONS, | | | PLEASE SEE OVEN, COOKTOP? GARAGE DR | | | OPENER,SPA TUB , BBQ FRIG, ETC. | | | 215.5,220.31 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|