2004-11-12 00:00:00******** PROVISO/REVISION *********
  
 1)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE SEE HEAT PUMP WHICH IS
 SHOWN ON LOAD CALCULATIONS IS NOT LISTED
 ON PANEL SCHEDULE. PLEASE LIST, OCP, AWG
 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND STAMPING ALONG WITH ANY OTHER
 REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  