| Plan Review Notes For Permit 04101185 |
| Permit Number |
04101185 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-12 00:00:00 | ******** PROVISO/REVISION ********* | | | | | | 1)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210.52 | | | | | | | | | 2 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | 3)NOTE: PLEASE SEE HEAT PUMP WHICH IS | | | SHOWN ON LOAD CALCULATIONS IS NOT LISTED | | | ON PANEL SCHEDULE. PLEASE LIST, OCP, AWG | | | ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND STAMPING ALONG WITH ANY OTHER | | | REVISIONS BEFORE ROUGH ELECTRICAL | | | INSPECTION.IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|