Plan Review Notes
Plan Review Notes For Permit 04101171
Permit Number 04101171
Review Stop B
Sequence Number 1
Notes
Date Text
2004-11-30 00:00:00BUILDING PLAN REVIEW FAILED
  
 1. ACCORDING TO FS471.023 & FAC
 61G15.23.002 ALL TITLE BLOCKS MUST
 INCLUDE THE CA# OF THE FIRM SHOWN ON
 THE TITLE BLOCK IN ADDITION TO THE
 INDIVIDUAL ENGINEER'S PE #. THE CA# FOR
 WEYANT AND ASSOCIATES, INC. IS NOT
 INCLUDED ON THE PLANS. THIS CAN BE HAND
 WRITTEN.
  
 2. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT COUNTY CLERK OFFICE &
 SUBMITTED
 BEFORE A PERMIT CAN BE PRINTED.
  
 3. NEED PROOF OF OWNERSHIP.
  
 4. THE FLORIDA ENERGY EFFICIENCY CODE
 SQ. FT. DOES NOT AGREE WITH THE PLANS.
 SEE LINES 6 & 10A.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713