| Plan Review Notes For Permit 04101144 |
| Permit Number |
04101144 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-06-15 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE CORRELATE LOAD SHOWN ON | | | PANEL "B" FOR POOL PANEL WITH LOAD SHOWN | | | ON POOL PANEL. | | | | | | PLEASE ALSO SEE LOAD SHOWN FOR PANEL "A" | | | AFTER DERATING, SHOWS LOAD EXCEEDING | | | RATING OF PANEL. PLEASE SEE 153.83A'S ON | | | A 150A PANEL. | | | | | | 240.4, ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|