2005-06-15 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE LOAD SHOWN ON
 PANEL "B" FOR POOL PANEL WITH LOAD SHOWN
 ON POOL PANEL.
  
 PLEASE ALSO SEE LOAD SHOWN FOR PANEL "A"
 AFTER DERATING, SHOWS LOAD EXCEEDING
 RATING OF PANEL. PLEASE SEE 153.83A'S ON
 A 150A PANEL.
  
 240.4, ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  