Plan Review Notes
Plan Review Notes For Permit 04101144
Permit Number 04101144
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-1 THE SANITARY RISER DIAGRAM
 TAPED TO THE SHEET DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS.
 A) THE SHOWER IN BATH #2 IS NOT
 VENTED.
 SECTION 902.1
 B) THE WASH MACHINE SHALL CONNECT
 DOWNSTREAM OF THE LAUNDRY SINK ON THE
 RISER. SECTION 901.2
 C) A CLEANOUT IS REQUIRED 4' ABOVE THE
 FLOOR ON THE WASH MACHINE RISER.
 SECTION
 708.10
 D) SHOW ALL PIPE SIZES. SECTION
 104.2.1
 E) THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FIXTURE OR PIPE LAYOUR ON
 SHEET A-1. SINK AT SUMMER KITCHEN IS
 NOT
 SHOWN AND THE PIPING IS SHOWN ENTERING
 THE HOUSE ON THE OPPOSITE END OF THE
 HOUSE. IF THE PIPING IS BEING INSTALLED
 FROM THE LEFT SIDE OF THE HOUSE THEN
 THE
 PIPING LAYOUT SHALL BE SHOWN TO REFLECT
 THE PIPING AS IT WILL BE INSTALLED.
 SECTION 104.2.1 - TAPEING THE RISER
 DIAGRAM OVER INFORMATION FOR THE
 FOUNDATION IS NOT APPROVED. SUBMIT NEW
 SHEET WITH RISER DIAGRAM SHOWN ON THE
 SHEET AND NOT COVERING OTHER INFORMATION
 SECTION 104.2.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]