| Plan Review Notes For Permit 04101144 |
| Permit Number |
04101144 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A-1 THE SANITARY RISER DIAGRAM | | | TAPED TO THE SHEET DOES NOT REFLECT THE | | | FLOOR PLAN, NOR DOES IT MEET CODE | | | REQUIREMENTS. | | | A) THE SHOWER IN BATH #2 IS NOT | | | VENTED. | | | SECTION 902.1 | | | B) THE WASH MACHINE SHALL CONNECT | | | DOWNSTREAM OF THE LAUNDRY SINK ON THE | | | RISER. SECTION 901.2 | | | C) A CLEANOUT IS REQUIRED 4' ABOVE THE | | | FLOOR ON THE WASH MACHINE RISER. | | | SECTION | | | 708.10 | | | D) SHOW ALL PIPE SIZES. SECTION | | | 104.2.1 | | | E) THE SANITARY RISER DIAGRAM DOES NOT | | | REFLECT THE FIXTURE OR PIPE LAYOUR ON | | | SHEET A-1. SINK AT SUMMER KITCHEN IS | | | NOT | | | SHOWN AND THE PIPING IS SHOWN ENTERING | | | THE HOUSE ON THE OPPOSITE END OF THE | | | HOUSE. IF THE PIPING IS BEING INSTALLED | | | FROM THE LEFT SIDE OF THE HOUSE THEN | | | THE | | | PIPING LAYOUT SHALL BE SHOWN TO REFLECT | | | THE PIPING AS IT WILL BE INSTALLED. | | | SECTION 104.2.1 - TAPEING THE RISER | | | DIAGRAM OVER INFORMATION FOR THE | | | FOUNDATION IS NOT APPROVED. SUBMIT NEW | | | SHEET WITH RISER DIAGRAM SHOWN ON THE | | | SHEET AND NOT COVERING OTHER INFORMATION | | | SECTION 104.2.1 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|