| 2004-12-02 00:00:00 | BUILDING PLAN REVIEW: FAILED |
| | |
| | 1.VALUE OF THE HOUSE HAS BEEN INCREASED |
| | AND THE ADDITIONAL FEES ARE $898.09 |
| | |
| | 2. PLANS MUST BE TAKEN TO PBC AND IMPACT |
| | FEES PAID.THE RECEIPT MUST BE |
| | SUBMITTED BEFORE A PERMIT CAN BE |
| | ISSUED. |
| | |
| | 3. SUBMIT ENGINEERING FOR THE BUTT GLASS |
| | LOCATED IN THE CAFE. THE ARCHITECT OR |
| | ENGINEER MUST PERFORM AN ON SITE |
| | INSPECTION OF THE BUTT GLASS ASSEMBLY & |
| | SUBMIT A LETTER SIGNED & SEALED STATING |
| | IT HAS BEEN INSTALLED PER HIS |
| | SPECIFICATIONS. THE PRODUCT APPROVAL WAS |
| | NOT SUBMITTED. FLORIDA PRODUCT OR |
| | LOCAL/SITE SPECIFIC REQUIRED. |
| | |
| | 4. THE GLASS BLOCK WILL REQUIRE |
| | HURRICANE PROTECTION THE WINDOW SCHEDULE |
| | DID NOT NOTE THE SHUTTERS WERE |
| | REQUIRED. |
| | |
| | 5. THE GARAGE DOORS ON THE PLANS ARE ALL |
| | THE SAME SIZE. THERE WERE TWO DIFFERENT |
| | FLORIDA PRODUCT APPROVALS SUBMITTED. |
| | REMOVE THE APPROVAL THAT DOES NOT APPLY. |
| | THERE WERE SEVERAL COPIES OF TO FL605. |
| | ONLY ONE PRODUCT APPROVAL IS REQUIRED |
| | WHEN THERE ARE SEVERAL PRODUCTS OF THE |
| | SAME KIND. THE OTHER PRODUCT APPROVAL IS |
| | FL1822. |
| | |
| | 6. SUBMIT THE MANUFACTURERS |
| | SPECIFICATIONS FOR THE GAS FIREPLACE IN |
| | THE FAMILY ROOM. |
| | |
| | 7. SUBMIT THE FLORIDA PRODUCT APPROVAL |
| | FOR THE 2 SINGLE LITE IMPACT FRENCH |
| | DOORS SHOWN AS DOOR #1 IN DOOR |
| | SCHEDULE. |
| | |
| | 8. THE SHUTTER SCHEDULE SHOWS DOOR #4 AS |
| | A METAL DOOR NOT TO BE COVERED. PLANS & |
| | DOOR SCHEDULE SHOW THE DOOR TO BE A |
| | SINGLE LITE FRENCH DOOR TO BE COVERED |
| | WITH STORM PANELS. PLEASE CLARIFY. |
| | |
| | 9. SUBMIT THE FLORIDA PRODUCT APPROVAL |
| | FOR THE STRUCTURAL COMPONENTS (TRUSS |
| | STRAPS, "USP" RT18F, HC10, RT20, ETC.) |
| | SEE SHEET A-7. |
| | |
| | ANY QUESTIONS PLEASE CALL: |
| | LEA SMITH, BUILDING PLANS EXAMINER |
| | 805-6713 |
| | |
| | |