Plan Review Notes
Plan Review Notes For Permit 04101133
Permit Number 04101133
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-12 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 AT THIS TIME SHOWING NEW MIN CIRCUITS.
 PLEASE INCLUDE AWG, OCP, ETC
 215.5
 PLEASE INDICATE SIZE OF EXSITNG
 SERVICE,PLANS NOTE: TO VERIFY?
 THIS IS REQUIRED AT THIS TIME.
  
 2)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 REQUIRED TO BE 20A, #12.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SEE 220.18 FOR MIN DRYER LOAD.
 PLEASE INCLUDE ALL EXISTING LOADS ALONG
 WITH NEW.
 ** LOAD CALCS DO NOT INDICATE, ANY
 PUMPS, WATER HEATERS, DISP, DISHWASHER,
 FRIG, ETC ??220.3C1
  
 4)NOTE: PLEASE SEE 2002 NEC 210.12 FOR
 THE REQUIRED ARC FAULT PROTECTION.
 SD,LTS, FANS,RECEPTS,,,,
  
 5)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G1-16.004. PLEASE SEE FS 481.219 FOR
 REQUIRED CA #'S.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMEENT IS
 MADE BY OTHER REVIEWER(S).
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PELASE DO NOT HESITATE TO CALL.
  