| 2005-07-29 00:00:00 | *********** UNSAT 4TH REVIEW *********** |
| | |
| | *************************************** |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES ONCE AGAIN DUE |
| | TO CHANGES IN PLANS. |
| | *************************************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS HAVE NOW COME |
| | BACK IN WITH A COMPLETELY NEW RISER. |
| | PLEASE SEE NEW NEW MLO METER/MAIN SHOWN. |
| | PLEASE CLARIFY 400A?? THIS IS ONLY A |
| | NOTE: |
| | PLEASE SEE A MCB WILL BE REQUIRED AS |
| | THERE MAY NOT BE ANY MORE THAN 6 SPACES |
| | IN A SINGLE ENCLOSURE.230.71 |
| | PLEASE SEE NEW COMMENT FOR GROUNDING |
| | ELECTRODE SYSTEM DUE TO INCREASE IN |
| | SERVICE. |
| | |
| | 2)NOTE: AS REQUESTED ON PREVIOUS REVIEW, |
| | ALL AIC RATINGS FOR NEW MAIN/ PANELS ETC |
| | SHALL BE SUBMITTED. 110.9, 215.5 |
| | PLEASE SEE ABOVE, ALL MAINS, BRKRS |
| | PANELS ARE TO BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT. |
| | |
| | 3)NOTE: PLEASE SEE NOTE #3 FROM ALL |
| | PREVIOUS REVIEWS. PLEASE SEE 220.31B FOR |
| | LOAD CALCULATIONS. |
| | THIS WAS GONE OVER IN MEETING WITH |
| | ARCHITECT AND ELECTRICIAN,HOWEVER ONLY |
| | PART OF THE CALCULATIONS ARE NOW |
| | CORRECTED? |
| | PLEASE SEE THIS HAS BEEN THE SAME |
| | COMMENT NOW FOR FOUR(4) REVIEWS.????? |
| | |
| | 4)NOTE: PLEASE SEE 210.52D,210.11C3 THE |
| | REQUIRED DEDICATED BATH CIRCUIT(S) ARE |
| | TO BE LISTED ON PANEL SCHEDULE AS |
| | PREVIOUSLY NOTED.?? |
| | |
| | 5)NOTE: PLEASE SEE ARC FAULT PROTECTION |
| | IS STILL LISTED FOR PROTECTION OF |
| | "RECEPT'S". PLEASE SEE THIS WAS REDLINED |
| | ON PLANS AND MEETING WITH ARCHITECT AND |
| | ELECTRICAN TO CORRECT TO THE 2002 NEC |
| | 210.12. PLEASE SEE THE 2002 NEC |
| | REQUIREMENT FOR THIS WAS ADOPTED BY THE |
| | STATE ON JULY 1ST, 2003. |
| | PLEASE SEE ARC FAULT PROTECTION IS |
| | REQUIRED FOR ALL "OUTLETS", THIS |
| | INCLUDES LTS, RECEPTS, FANS, SD'S ETC. |
| | |
| | 6)NOTE: PLEASE SEE DUE TO CHANGE AND |
| | INCREASE IN SERVICE TO 400A'S? , PLEASE |
| | SEE GROUNDINGELECTRODE CONDUCTOR SHALL |
| | BE SIZED PER TABLE 250.66 IN THE NEC, |
| | BASED ON MIN SEC'S FROM 310.15B6 |
| | PLEASE SEE IF SERVICE STAYS AT 400A'S, A |
| | MIN. OF A 1/0 SHALL BE USED. |
| | PLEASE CORRECT. |
| | |
| | 7)NOTE: PLEASE SEE AS NOTED ON (3)THREE |
| | PREVIOUS REVIEWS, A 4X FEE SHALL BE |
| | ACCESSED PER FS 553.80(2)(B)TO ALL |
| | REPEAT COMMENTS. PLEASE SEE THIS IS |
| | REQUIRED UNDER STATE STATUE AND IS NOT A |
| | LOCAL RULE OR FEE. THIS IS PER |
| | FS553.80(2)(B) WITH RESPECT TO THE |
| | DESIGN PROFESSIONL. PLEASE SEE A COPY |
| | TAKEN DIRECTLY FROM THE FS WAS ATTACHED |
| | FOR THE LAST TWO REVIEWS. |
| | PLEASE SEE LOAD CALCULATIONS AND |
| | POSSIBEL "MISPRINT". |
| | IT IS STRONGLY SUGGESTED A MEETING BE |
| | SCHEDULED TO GO OVER COMMENTS. |
| | PLANS MAY BE TURNED OVER TO THE STATE |
| | BOARD OF ARCHITECTS FOR REVIEW. |
| | ONE COPY OF ELECTRICAL PLANS IS NOW |
| | RETAINED FOR FILE. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF ANY VOIDED/OLD |
| | COPIES FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | |