Plan Review Notes
Plan Review Notes For Permit 04101063
Permit Number 04101063
Review Stop E
Sequence Number 4
Notes
Date Text
2005-07-29 00:00:00*********** UNSAT 4TH REVIEW ***********
  
 ***************************************
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES ONCE AGAIN DUE
 TO CHANGES IN PLANS.
 ***************************************
  
 1)NOTE: PLEASE SEE PLANS HAVE NOW COME
 BACK IN WITH A COMPLETELY NEW RISER.
 PLEASE SEE NEW NEW MLO METER/MAIN SHOWN.
 PLEASE CLARIFY 400A?? THIS IS ONLY A
 NOTE:
 PLEASE SEE A MCB WILL BE REQUIRED AS
 THERE MAY NOT BE ANY MORE THAN 6 SPACES
 IN A SINGLE ENCLOSURE.230.71
 PLEASE SEE NEW COMMENT FOR GROUNDING
 ELECTRODE SYSTEM DUE TO INCREASE IN
 SERVICE.
  
 2)NOTE: AS REQUESTED ON PREVIOUS REVIEW,
 ALL AIC RATINGS FOR NEW MAIN/ PANELS ETC
 SHALL BE SUBMITTED. 110.9, 215.5
 PLEASE SEE ABOVE, ALL MAINS, BRKRS
 PANELS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
  
 3)NOTE: PLEASE SEE NOTE #3 FROM ALL
 PREVIOUS REVIEWS. PLEASE SEE 220.31B FOR
 LOAD CALCULATIONS.
 THIS WAS GONE OVER IN MEETING WITH
 ARCHITECT AND ELECTRICIAN,HOWEVER ONLY
 PART OF THE CALCULATIONS ARE NOW
 CORRECTED?
 PLEASE SEE THIS HAS BEEN THE SAME
 COMMENT NOW FOR FOUR(4) REVIEWS.?????
  
 4)NOTE: PLEASE SEE 210.52D,210.11C3 THE
 REQUIRED DEDICATED BATH CIRCUIT(S) ARE
 TO BE LISTED ON PANEL SCHEDULE AS
 PREVIOUSLY NOTED.??
  
 5)NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS STILL LISTED FOR PROTECTION OF
 "RECEPT'S". PLEASE SEE THIS WAS REDLINED
 ON PLANS AND MEETING WITH ARCHITECT AND
 ELECTRICAN TO CORRECT TO THE 2002 NEC
 210.12. PLEASE SEE THE 2002 NEC
 REQUIREMENT FOR THIS WAS ADOPTED BY THE
 STATE ON JULY 1ST, 2003.
 PLEASE SEE ARC FAULT PROTECTION IS
 REQUIRED FOR ALL "OUTLETS", THIS
 INCLUDES LTS, RECEPTS, FANS, SD'S ETC.
  
 6)NOTE: PLEASE SEE DUE TO CHANGE AND
 INCREASE IN SERVICE TO 400A'S? , PLEASE
 SEE GROUNDINGELECTRODE CONDUCTOR SHALL
 BE SIZED PER TABLE 250.66 IN THE NEC,
 BASED ON MIN SEC'S FROM 310.15B6
 PLEASE SEE IF SERVICE STAYS AT 400A'S, A
 MIN. OF A 1/0 SHALL BE USED.
 PLEASE CORRECT.
  
 7)NOTE: PLEASE SEE AS NOTED ON (3)THREE
 PREVIOUS REVIEWS, A 4X FEE SHALL BE
 ACCESSED PER FS 553.80(2)(B)TO ALL
 REPEAT COMMENTS. PLEASE SEE THIS IS
 REQUIRED UNDER STATE STATUE AND IS NOT A
 LOCAL RULE OR FEE. THIS IS PER
 FS553.80(2)(B) WITH RESPECT TO THE
 DESIGN PROFESSIONL. PLEASE SEE A COPY
 TAKEN DIRECTLY FROM THE FS WAS ATTACHED
 FOR THE LAST TWO REVIEWS.
 PLEASE SEE LOAD CALCULATIONS AND
 POSSIBEL "MISPRINT".
 IT IS STRONGLY SUGGESTED A MEETING BE
 SCHEDULED TO GO OVER COMMENTS.
 PLANS MAY BE TURNED OVER TO THE STATE
 BOARD OF ARCHITECTS FOR REVIEW.
 ONE COPY OF ELECTRICAL PLANS IS NOW
 RETAINED FOR FILE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY VOIDED/OLD
 COPIES FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]