| Date |
Text |
| 2005-06-13 00:00:00 | ************ UNSAT 3RD REVIEW ********* |
| | |
| | PLEASE SEE NOTES FROM PREVISOUS REVIEWS |
| | AND NOTES CONTAINED IN THIS THIRD |
| | REVIEW. |
| | |
| | 1)NOTE: NO, |
| | PLEASE SEE NOW A COMPLETE NEW RISER |
| | DIAGRAM IS NOW SUBMITTED SHOWING ALL |
| | PANELS/SERVICE AS NEW?? |
| | PLEASE SEE BOTH SUB PANELS ARE SHOWN AS |
| | T.L.O'S ?? IS THIS SUPPOSE TO BE MLO? |
| | PLEASE SEE THESE PANELS ARE NOW MISSING |
| | EQUIPMENT GROUNDING CONDUCTORS FROM |
| | MCB/PANEL "A" PER 250.122,250.110,250.24 |
| | ETC. |
| | |
| | 2)NOTE: PLEASE SEE SINCE ALL THESE |
| | PANELS ARE NOW SHOWN AS NEW , PLEASE |
| | SUBMIT AIC RATINGS FOR AL0 EQUIPMENT, |
| | MAINS/PANELS/ BRKRS ARE ALL TO BE RATED |
| | FOR THE AVAILABLE FAULT CURRENT PER |
| | 110.9/215.5 |
| | |
| | 3)NOTE: PLEASE SEE NOTE # 3 FROM TWO |
| | PREVIOUS REVIEWS. PLEASE SEE 220.31B FOR |
| | LOAD CALCULATIONS OF EXISTING LOADS AND |
| | NEW LOADS/HEATING ETC ADDED. |
| | |
| | 4)NOTE: PLEASE SEE A SUB PANEL IS NOW |
| | SHOWN IN THE CLOTHES CLOSET, PLEASE SEE |
| | 240.24D, 408.7, PANELS ARE SHALL NOT BE |
| | INSTALLED IN CLOTHES CLOSET. |
| | |
| | 5)NOTE: PLEASE SEE PREVIOUS REVIEW |
| | MENTIONED FS 553.80(2)(B) WITH RESPECT |
| | TO THE DESIGN PROFESSIONAL AND REPEAT |
| | COMMENTS. A NOTICE WAS GIVEN IF PLANS |
| | CAME BACK WITH ANY OF THE COMMENTS |
| | REPEATED FROM TWO PREVIOUS REVIEW NOT |
| | ADDRESSED, A 4X FEE FOR THE PLAN REVIEW |
| | PORTION OF THE PERMIT FEE WOULD BE |
| | ACCESSED. PLEASE SEE A FEE IS NOW |
| | ACCESSED AS REQUIRED UNDER FS |
| | 553.80(2)(B) IN THE AMOUNT OF $1320.00. |
| | PLEASE SEE FS WHICH REQUIRES THIS TO BE |
| | PAID BEFORE PLANS MAY BE RESUBMITTED. |
| | THIS FEE IS ACCESSED TO THE DESIGN |
| | PROFESSIONAL AND NOT THE HOME OWNER OR |
| | CONTRACTOR OF RECORD. |
| | PLEASE NOTE: AS OF THIS REVIEW, NO ONE |
| | HAS CALLED TO GO OVER ANY QUESTIONS ON |
| | THIS PROJECT. |
| | |
| | 6)NOTE: PLEASE LIST THE REQUIRED BATH |
| | CIRCUIT AS #12, 20A 210.52D ,210.11C3 |
| | |
| | 7)NOTE: PLEASE SEE NOT ALL SHEETSARE |
| | SIGNED THE SAME WAY BY THE ARCH, PLEASE |
| | ALSO SEE SOME SHEETS NOT SIGNED AND |
| | SEALED . |
| | FS 481.221 |
| | |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE ONE SET OF OLD SHEETS ARE TO |
| | BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |