| 2005-03-15 00:00:00 | ********* UNSAT 2ND REVIEW ************ |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE SEE RISER |
| | DIAGRAM NOW SHOWS A NEW 150A MCB PANEL. |
| | WHERE IS THIS FED FROM? PLEASE SEE |
| | EXISTING 200A PANEL DOES NOT INDICATE |
| | ANY FEED TO NEW PANEL BY MEANS OF OCP, |
| | CONDUIT, CONDUCTOR SIZE ETC. |
| | PLEASE SEE MANY ITEMS SHOWN ON PANEL |
| | SCHEDULE WHICH NEED TO CORRELATE OCP, |
| | KW/LOAD, AND AWG. |
| | PLEASE SEE THESE ITEMS REDLINED. |
| | 10KW ON 20A OCP, 5500 KW FOR 10KW LOAD, |
| | 20A OCP ON #6ETC. |
| | |
| | 2)NOTE: NOTE #2, OK. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE 220.31B |
| | FOR LOAD CALCUALTIONS TO AN EXISTING |
| | SERVICE/DWELLING. |
| | PLEASE SUBMIT LOAD CALCS ON SERVICE |
| | ALONG WITH LOAD ON EACH PANEL. |
| | |
| | 4)NOTE: NOTE #4 OK |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE # NO. SEE PREVIOUS NOTES. |
| | |
| | 7)NOTE #7 NO, PLEASE SEE 2002 NEC |
| | 210.12, NOTE MENTIONS RECEPTS? THIS WAS |
| | OLD REQUIREMENT. |
| | |
| | NEW NOTE: |
| | |
| | 1)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FS553.80(2)(B) WITH RESPECT TO THE |
| | DESIGN PROFESSIONAL. |
| | |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |