2004-11-29 00:00:00DENIED:
 1.PROVIDE A COMPLETED FORM 600C PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 6 METHOD
 C.
  
 2.PROVIDE EQUIPMENT SCHEDULE.
 INDICATE IF THE A/C EQUIPMENT IS NEW OR
 EXISTING.
  
 3.PROVIDE DUCT/GRILLE SIZE AND
 LAYOUT.
  
 4.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE GRILLE INDICATED IN THE "NEW
 SUMMER KITCHEN".INDICATE IF THE GRILLE
 IS GAS OR ELECTRIC.PROVIDE VENTING
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  