| 2004-11-12 00:00:00 | ******* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | WITH RISER. RISER/PANEL INDICATES A |
| | "DOUBLE-TUB" (FEED-THRU) PANEL. |
| | YET PANEL SCHEDULE ONLY INDICATES 38 |
| | CIRCUITS?? |
| | PLEASE INDICATE NEW AND EXISTING |
| | CIRCUITS. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SHOW LOCATION OF COND |
| | UNIT ON PLANS FOR NEW A/C SYSTEM. PLEASE |
| | SHOW DISC PER 440.11. |
| | PLEASE SEE 210.63 FOR MISSING SERVICE |
| | RECEPT FOR COND UNIT AND AHU? |
| | |
| | 3)NOTE: PLEASE SEE 220.31B FOR ADDITION |
| | OF HEAT LOADS TO EXSITING SERVICE. |
| | PLEASE RE-FIGURE LOAD CALCS. |
| | |
| | 4)NOTE: PLEASE INCLUDE FOOTER STEEL AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | 250.50 |
| | |
| | 5)NOTE: PLEASE INCLUDE PRINTED LICENSE # |
| | ON TITLE BLOCK AS REQUIRED UNDER FAC |
| | 61G1-16.004 |
| | |
| | 6)NOTE: PLEASE SEE FBC CHAPTER 34, FOR |
| | ADDITIONS TO EXISTING DWELLINGS. |
| | PLEASE SHOW LAYOUT FOR SD'S AND GFI |
| | PROTECTED RECEPTS REQUIRED UNDER CURRENT |
| | 2002 NEC AND NFPA-72 8-1.4.1.6.2 |
| | FBC 3401.7.1.2.1 |
| | |
| | 7)NOTE: ARC FAULT PROTECTION REQUIRED |
| | FOR NEW BEDRM ELECTRICAL DEVICES. |
| | 2002 NEC 210.12 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |