Plan Review Notes
Plan Review Notes For Permit 04101063
Permit Number 04101063
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-12 00:00:00******* UNSAT **************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 WITH RISER. RISER/PANEL INDICATES A
 "DOUBLE-TUB" (FEED-THRU) PANEL.
 YET PANEL SCHEDULE ONLY INDICATES 38
 CIRCUITS??
 PLEASE INDICATE NEW AND EXISTING
 CIRCUITS.
 215.5
  
 2)NOTE: PLEASE SHOW LOCATION OF COND
 UNIT ON PLANS FOR NEW A/C SYSTEM. PLEASE
 SHOW DISC PER 440.11.
 PLEASE SEE 210.63 FOR MISSING SERVICE
 RECEPT FOR COND UNIT AND AHU?
  
 3)NOTE: PLEASE SEE 220.31B FOR ADDITION
 OF HEAT LOADS TO EXSITING SERVICE.
 PLEASE RE-FIGURE LOAD CALCS.
  
 4)NOTE: PLEASE INCLUDE FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 5)NOTE: PLEASE INCLUDE PRINTED LICENSE #
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G1-16.004
  
 6)NOTE: PLEASE SEE FBC CHAPTER 34, FOR
 ADDITIONS TO EXISTING DWELLINGS.
 PLEASE SHOW LAYOUT FOR SD'S AND GFI
 PROTECTED RECEPTS REQUIRED UNDER CURRENT
 2002 NEC AND NFPA-72 8-1.4.1.6.2
 FBC 3401.7.1.2.1
  
 7)NOTE: ARC FAULT PROTECTION REQUIRED
 FOR NEW BEDRM ELECTRICAL DEVICES.
 2002 NEC 210.12
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  