| Date |
Text |
| 2004-11-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A1 OF 3 GENERAL NOTES #1 STATES |
| | "STANDARD BUILDING CODE", ADOPTED CODE |
| | IS FBC-2001 BUILDING. PLEASE CHANGE |
| | REFERENCE. SECTION 104.2.1 |
| | 2) ROUTE THE PLANS TO DBPR DIVISION OF |
| | HOTELS AND RESTURANT FOOD LICENSE |
| | SERVICE FOR REVIEW. A MINIMUM OF 2 |
| | STAMPED SETS SHALL BE RETURNED FOR |
| | REVIEW WITH THE WORKSHEETS ATTACHED. |
| | SECTION 101.4.7. |
| | 3) GREASE INTERCEPTOR SHALL BE SIZED BY |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| | (561) 837-4074. ATTACH THE DETERMINE |
| | SHEET FROM MR. COMPO TO PLANS WHEN |
| | RESUBMITTING. WASTE ORD. #3928-95 |
| | 4) SHT M1 OF 3 PLUMBING NOTES: |
| | #1 STATES STANDARD BUILDING CODE - |
| | ADOPTED CODE IS FBC-2001 PLUMBING. |
| | CHANGE REFERENCE. SECTION 104.2.1 |
| | #8 PIPE 2-1/2" AND SMALLER SHALL BE |
| | SLOPED AT 1/4" PER FT. TABLE 704.1 |
| | #12 AIR CHAMBERS ARE NOT APPROVED. |
| | REMOVE FROM REFERENCE. SECTION 604.9 - |
| | ALSO NOTE INDICATES THAT SHOCK ARRESTORS |
| | WILL BE INSTALLED. SHOW THE SHOCK |
| | ARRESTORS ON THE WATER RISER, PER PDI-WH |
| | 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS |
| | 5) SHT M1 OF 3 GREASE TRAP DETAIL, TWO |
| | WAY CLEANOUTS ARE REQUIRED AT THE INLET |
| | AND THE OUTLET SIDES OF THE GREASE TRAP. |
| | THE LIDS SHALL BE STAMPED "GREASE". SEE |
| | ATTACHED UTILITY WPB GREASE TRAP |
| | DETAIL. |
| | 6) THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - NOT ALL LENGHT OF PIPE |
| | ARE SHOWN. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 7) SUBMIT A DETAIL FOR THE ACCESSIBLE |
| | TOILET ROOM PER SECTIONS 11-4.16, |
| | 11-4.19, & 11-4.22 AND ALL SUBSECTIONS. |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |