Plan Review Notes
Plan Review Notes For Permit 04101050
Permit Number 04101050
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A1 OF 3 GENERAL NOTES #1 STATES
 "STANDARD BUILDING CODE", ADOPTED CODE
 IS FBC-2001 BUILDING. PLEASE CHANGE
 REFERENCE. SECTION 104.2.1
 2) ROUTE THE PLANS TO DBPR DIVISION OF
 HOTELS AND RESTURANT FOOD LICENSE
 SERVICE FOR REVIEW. A MINIMUM OF 2
 STAMPED SETS SHALL BE RETURNED FOR
 REVIEW WITH THE WORKSHEETS ATTACHED.
 SECTION 101.4.7.
 3) GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 837-4074. ATTACH THE DETERMINE
 SHEET FROM MR. COMPO TO PLANS WHEN
 RESUBMITTING. WASTE ORD. #3928-95
 4) SHT M1 OF 3 PLUMBING NOTES:
 #1 STATES STANDARD BUILDING CODE -
 ADOPTED CODE IS FBC-2001 PLUMBING.
 CHANGE REFERENCE. SECTION 104.2.1
 #8 PIPE 2-1/2" AND SMALLER SHALL BE
 SLOPED AT 1/4" PER FT. TABLE 704.1
 #12 AIR CHAMBERS ARE NOT APPROVED.
 REMOVE FROM REFERENCE. SECTION 604.9 -
 ALSO NOTE INDICATES THAT SHOCK ARRESTORS
 WILL BE INSTALLED. SHOW THE SHOCK
 ARRESTORS ON THE WATER RISER, PER PDI-WH
 201 AND MANUF. INSTALLATION
 INSTRUCTIONS
 5) SHT M1 OF 3 GREASE TRAP DETAIL, TWO
 WAY CLEANOUTS ARE REQUIRED AT THE INLET
 AND THE OUTLET SIDES OF THE GREASE TRAP.
 THE LIDS SHALL BE STAMPED "GREASE". SEE
 ATTACHED UTILITY WPB GREASE TRAP
 DETAIL.
 6) THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL LENGHT OF PIPE
 ARE SHOWN.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 7) SUBMIT A DETAIL FOR THE ACCESSIBLE
 TOILET ROOM PER SECTIONS 11-4.16,
 11-4.19, & 11-4.22 AND ALL SUBSECTIONS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]