2004-11-16 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.PLAN SHEET M1 OF 3 INDICATES GAS
 LOAD CALCULATIONS PER NATIONAL FUEL GAS
 CODE 1999 EDITION.THIS SHOULD READ
 2001 FBC, FUEL GAS.
  
 ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION, GAS, AND WALK-IN
 COOLERS.PROVIDE PLANS & MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
 PROVIDE SUBMITTAL FOR THE CONVECTION
 OVEN INDICATED ON M1 OF 3.
  
 3.PLANS ARE TO BE APPROVED BY DBPR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.