| Date |
Text |
| 2004-11-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) FIRST SHEET GENERAL NOTES #1 STATES |
| | "STANDARD BUILDING CODE", ADOPTED CODE |
| | IS THE FLORIDA BUILDING CODE-2001. |
| | PLEASE UPDATE REFERENCE. |
| | 2) PLANS SHALL BE ROUTED TO DBPR, STATE |
| | OF FLORIDA DEPT. OF BUSINESS REGULATION, |
| | DIVISION OF HOTEL AND RESTURANT FOR |
| | REVIEW. SUBMIT 2 OR MORE SETS OF PLANS |
| | STAMPED BY DBPR REVIEW WITH "WORKSHEETS" |
| | ATTACHED FOR REVIEW. SECTION 101.4.7 |
| | 3) GREASE INTECEPTOR SHALL BE SIZED BY |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| | A DETERMINATION SHEET FROM R. COMPO |
| | SHALL BE ATTACHED TO PLANS WHEN |
| | RESUBMITTING FOR REVIEW. CONTACT MR. |
| | COMPO AT (561) 837-4074. WASTE ORD. |
| | #2938-95 |
| | 4) SEE ATTACHED SHEET FOR APPROVED |
| | GREASE INTERCEPTOR DETAIL. |
| | 5) SHT M1 0F 3 PLUMBING NOTES #1 |
| | INDICATES STANDARD PLUMBING CODE, |
| | APPROVED CODE IS FBC-2001 PLUMBING. |
| | UPDATE REFERENCE. SECTION 104.2.1 |
| | 6) SHT M1 OF 3 PLUMBING NOTES #8, 2-1/2" |
| | AND SMALLER PIPE SHALL SLOPE 1/4" PER |
| | FOOT. CORRECT PLUMBING REFERENCE. TABLE |
| | 704.1 |
| | 7) SHT M1 OF 3 PLUMBING NOTES #12 AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | REFERENCE. NOTE INDICATES THAT SHOCK |
| | ARRESTORS ARE TO BE USED. IF SO SHOW ON |
| | WATER RISER DIAGRAM. SECTIONS 604.9 AND |
| | 104.2.1 |
| | 8) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2 |
| | 9) TWO WAY CLEANOUTS ARE REQUIRED ON THE |
| | INLET AND EXIT OF THE GREASE INTERCEPTOR |
| | AND THE LIDS SHALL BE STAMPED WITH THE |
| | WORDS "GREASE". (SEE ATTACHED SHEET). |
| | 10) SHT M1 OF 3 STATES "NATIONAL FUEL |
| | GAS CODE 1999 EDITION", THE ADOPTED CODE |
| | FOR FUEL GAS IS FBC-2001 FUEL GAS. |
| | PLEASE CHANGE REFERENCE. SECTION |
| | 104.2.1 |
| | 11 THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS PERMIT REQUIRED . |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE.-NOT ALL LENGTHS ARE |
| | SHOWN |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF USED. |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| 2004-10-27 00:00:00 | TO COMM BD#20 |