Plan Review Notes
Plan Review Notes For Permit 04101050
Permit Number 04101050
Review Stop I
Sequence Number 1
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) FIRST SHEET GENERAL NOTES #1 STATES
 "STANDARD BUILDING CODE", ADOPTED CODE
 IS THE FLORIDA BUILDING CODE-2001.
 PLEASE UPDATE REFERENCE.
 2) PLANS SHALL BE ROUTED TO DBPR, STATE
 OF FLORIDA DEPT. OF BUSINESS REGULATION,
 DIVISION OF HOTEL AND RESTURANT FOR
 REVIEW. SUBMIT 2 OR MORE SETS OF PLANS
 STAMPED BY DBPR REVIEW WITH "WORKSHEETS"
 ATTACHED FOR REVIEW. SECTION 101.4.7
 3) GREASE INTECEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 A DETERMINATION SHEET FROM R. COMPO
 SHALL BE ATTACHED TO PLANS WHEN
 RESUBMITTING FOR REVIEW. CONTACT MR.
 COMPO AT (561) 837-4074. WASTE ORD.
 #2938-95
 4) SEE ATTACHED SHEET FOR APPROVED
 GREASE INTERCEPTOR DETAIL.
 5) SHT M1 0F 3 PLUMBING NOTES #1
 INDICATES STANDARD PLUMBING CODE,
 APPROVED CODE IS FBC-2001 PLUMBING.
 UPDATE REFERENCE. SECTION 104.2.1
 6) SHT M1 OF 3 PLUMBING NOTES #8, 2-1/2"
 AND SMALLER PIPE SHALL SLOPE 1/4" PER
 FOOT. CORRECT PLUMBING REFERENCE. TABLE
 704.1
 7) SHT M1 OF 3 PLUMBING NOTES #12 AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. NOTE INDICATES THAT SHOCK
 ARRESTORS ARE TO BE USED. IF SO SHOW ON
 WATER RISER DIAGRAM. SECTIONS 604.9 AND
 104.2.1
 8) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 9) TWO WAY CLEANOUTS ARE REQUIRED ON THE
 INLET AND EXIT OF THE GREASE INTERCEPTOR
 AND THE LIDS SHALL BE STAMPED WITH THE
 WORDS "GREASE". (SEE ATTACHED SHEET).
 10) SHT M1 OF 3 STATES "NATIONAL FUEL
 GAS CODE 1999 EDITION", THE ADOPTED CODE
 FOR FUEL GAS IS FBC-2001 FUEL GAS.
 PLEASE CHANGE REFERENCE. SECTION
 104.2.1
 11 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT REQUIRED .
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.-NOT ALL LENGTHS ARE
 SHOWN
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF USED.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]