Plan Review Notes
Plan Review Notes For Permit 04101050
Permit Number 04101050
Review Stop G
Sequence Number 1
Notes
Date Text
2006-01-23 00:00:00DENIED;
 A 2# TO 12" W.C. REGULATOR MUST BE
 INSTALLED AFTER THE WATER HEATER BRANCH
 AND WITHIN 60' OF THE LAST GAS APPLIANCE
 TO MEET THE REQUIREMENTS OF THE FBC-2001
 FUEL GAS TABLE 402(2). THE REQULATOR FOR
 THE WATER HEATER MUST BE A 2# BY 12"
 W.C. WITH A SHUTOFF VALVE UP STREAM AND
 A UNION DOWN STREAM OF THE REGULATOR.
 SEE ONE PLAN MARKED IN RED.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695