| 2004-11-02 00:00:00 | ************* UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE CORRELATE |
| | PLANS/PANEL/RISER. PLANS SHOWS 100A |
| | PANEL, YET RISER ETC SHOWS 150A |
| | |
| | 2)NOTE: PLEASE CLARIFY EQUIPMENT |
| | GROUNDING FROM MAIN TO PANEL. 250.110, |
| | 250.122 |
| | |
| | 3) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 4)NOTE: PLEASE IDENTIFY ALL RECEPTS IN |
| | KITCHEN AREA AS GFI/GFI PROTECTED PER |
| | 2002 NEC 210.8B3 |
| | |
| | 5)NOTE: PLEASE PROVIDE LOAD ON EXSITING |
| | 1200A MAIN SHOWN. 215.5,220 |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL SHEETS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | |
| | INSERT NEW SHEETS ONLY INTO TWO |
| | COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |