Plan Review Notes
Plan Review Notes For Permit 04101050
Permit Number 04101050
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-02 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE CORRELATE
 PLANS/PANEL/RISER. PLANS SHOWS 100A
 PANEL, YET RISER ETC SHOWS 150A
  
 2)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING FROM MAIN TO PANEL. 250.110,
 250.122
  
 3) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE IDENTIFY ALL RECEPTS IN
 KITCHEN AREA AS GFI/GFI PROTECTED PER
 2002 NEC 210.8B3
  
 5)NOTE: PLEASE PROVIDE LOAD ON EXSITING
 1200A MAIN SHOWN. 215.5,220
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL SHEETS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
  
 INSERT NEW SHEETS ONLY INTO TWO
 COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5