Plan Review Notes
Plan Review Notes For Permit 04101021
Permit Number 04101021
Review Stop M
Sequence Number 1
Notes
Date Text
2004-11-17 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES EXISTING
 DUCT PENETRATING TENANT SEPARATION WALL
 WHICH REQUIRES A FIRE DAMPER.PLEASE
 INDICATE ON PLAN ANY NEW OR EXISTING
 FIRE DAMPERS PER 2001 FBC(M) 607.6.
  
 2.PROVIDE REVISED OUTSIDE AIR
 CALUCALTIONS IN ACCORDANCE WITH 2001
 FBC(M)403.3.
  
 3.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  
  