| Plan Review Notes For Permit 04101021 |
| Permit Number |
04101021 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-17 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 INDICATES EXISTING | | | DUCT PENETRATING TENANT SEPARATION WALL | | | WHICH REQUIRES A FIRE DAMPER.PLEASE | | | INDICATE ON PLAN ANY NEW OR EXISTING | | | FIRE DAMPERS PER 2001 FBC(M) 607.6. | | | | | | 2.PROVIDE REVISED OUTSIDE AIR | | | CALUCALTIONS IN ACCORDANCE WITH 2001 | | | FBC(M)403.3. | | | | | | 3.NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM PER | | | 2001 FBC(M)602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. | | | | | | |
|