Plan Review Notes
Plan Review Notes For Permit 04101019
Permit Number 04101019
Review Stop E
Sequence Number 5
Notes
Date Text
2006-07-05 00:00:00*** UNSAT ***
  
 ** PLEASE SEE RISER IS NOW COMPLETELY
 DIFFERENT FROM PREVIOUS PLANS.
  
 1) NOTE: PLEASE INDICATE IF THE NEW
 PANEL "A" CONTAINS OCP FEEDING PANEL "C"
 OR DOES PANEL "A" CONTAIN FEED-THRU LUGS
 TO PANEL "C".
 215.5
  
 2) NOTE: PLEASE SEE SOME CIRCUITING ON
 PLANS EXCEED THE CIRCUITS SHOWN ON PANEL
 SCHEDULE "C". ( GDO).
 PLEASE ALSO KNOW THE GDO MAY NOT FEED
 OTHER ELECTRICAL LIGHTING/ DEVICES.
 430.31, TABLES 430.148
  
 3) NOTE: PLEASE SEE 408.4, AS THE PANEL
 SCHEDULES SHALL BE SPECIFIC ON BRANCH
 CIRCUITS. IE; BEDRM LTS, KITCHEN LTS,
 BATH LTS, LIV RM RECEPTS ETC.
  
 4) NOTE: PLEASE SEE KITCHEN PENINSULAR
 WHICH SHOWS A CIRCUIT "C-142' ?? WHAT IS
 THIS?
  
  
 ** PLEASE VERIFY THE FOLLOWING WHICH IS
 NOT A CODE VIOLATION, HOWEVER IF SHOWN
 THIS WAY ON PLANS, THEN THIS IS WHAT
 WILL BE REQUIRED.
 1) PLEASE VERIFY THE GEC ON RISER AS,
 1/0 IS BEING SHOWN?
 2) NOTE: PLEASE VERIFY MANY CIRCUITS
 SHOWN WITH #12 AND 15A BRKR.
 PLEASE CALL , IF THERE ARE ANY
 QUESTIONS, ON THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  