| Plan Review Notes For Permit 04101019 |
| Permit Number |
04101019 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-12-23 00:00:00 | *********** UNSAT ****************** | | | | | | PLEASE SEE THE FOLLOWING NOTES, WHICH | | | SOME ARE STILL FROM PREVIOUS REVIEW. | | | | | | 1)NOTE: PLEASE SEE NOTES #'S 4,5 AND 7 | | | FROM PREVIOUS REVIEW. PLEASE ALSO SEE | | | NOTE FOR LOAD CALCS. | | | | | | PLEASE SHOW GFI/GFI PROTECTION FOR ALL | | | RECEPTS REQUIRED TO BE GFI PROTECTED | | | UNDER 210.8. | | | | | | PLEASE SEE NOTE MANUFACTURE SPECS FOR | | | GEN/TRANSFER SWITCH/ EM PANEL ETC. | | | NOTE ON PLANS MENTIONS TO ALTER A UL | | | LISTED PREWIRED PANEL? | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GRNDS AFTER THE FIRST MEANS OF DISC. | | | 250.24,250.122 | | | | | | ** PLEASE SEE GENERATOR LOCATION NEEDS | | | TO BE SHOWN ON SITE/HOUSE PLANS. | | | | | | 3)NOTE: PLEASE SEE AN ATTACHED COPY OF | | | FS 553.80(2)(B) IS NOW ATTACHED. THIS | | | IS | | | GIVEN AS A NOTICE ONLY AT THIS TIME. | | | | | | 4)NOTE: PLEASE SEE NOTE ON BOTTOM OF | | | LOAD CALC MENTIONS EXISTING SERVICE , | | | YET RISER SHOWS NEW? | | | | | | 5)NOTE: PLEASE SEE 220.31B FOR LOAD | | | CALCS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|