2004-12-23 00:00:00*********** UNSAT ******************
  
 PLEASE SEE THE FOLLOWING NOTES, WHICH
 SOME ARE STILL FROM PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE NOTES #'S 4,5 AND 7
 FROM PREVIOUS REVIEW. PLEASE ALSO SEE
 NOTE FOR LOAD CALCS.
  
 PLEASE SHOW GFI/GFI PROTECTION FOR ALL
 RECEPTS REQUIRED TO BE GFI PROTECTED
 UNDER 210.8.
  
 PLEASE SEE NOTE MANUFACTURE SPECS FOR
 GEN/TRANSFER SWITCH/ EM PANEL ETC.
 NOTE ON PLANS MENTIONS TO ALTER A UL
 LISTED PREWIRED PANEL?
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GRNDS AFTER THE FIRST MEANS OF DISC.
 250.24,250.122
  
 ** PLEASE SEE GENERATOR LOCATION NEEDS
 TO BE SHOWN ON SITE/HOUSE PLANS.
  
 3)NOTE: PLEASE SEE AN ATTACHED COPY OF
 FS 553.80(2)(B) IS NOW ATTACHED. THIS
 IS
 GIVEN AS A NOTICE ONLY AT THIS TIME.
  
 4)NOTE: PLEASE SEE NOTE ON BOTTOM OF
 LOAD CALC MENTIONS EXISTING SERVICE ,
 YET RISER SHOWS NEW?
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]