Plan Review Notes
Plan Review Notes For Permit 04101019
Permit Number 04101019
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-22 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE 210.52C1 FOR RECEPT
 SPACING ALONG KITCHEN COUNTERSPACE.
  
 2)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU. PLEASE ALSO SEE 310.16 FOR
 SIZING OF CONDUCTORS.
  
 3)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
  
 4)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXSITNG DWELLINGS.
 PLEASE PROVIDE LAYOUT FOR NEW AND OR
 EXISTINGTO MEET 2002 NEC FOR GFI'S AND
 SD'S.
  
  
 5) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
  
 6)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 THIS IS A COMMON TEXT NOTE AND PLANS MAY
 NOT NEED TO MEET ALL OF THE ABOVE.
  
 7)NOTE: PLEASE SUBMIT COMPLETE SPEC
 SHEETS ON NEW PROPOSED GENERATOR
 SYSTEM.
 PLEASE BE AWARE WE ARE CURRENTLY HAVING
 SOME ISSUES W/CERTAIN "MANUFACTURED"
 PRE-WIRED SYSTEMS THAT DO NOT MEET CODE
 COMPLIANCE.
  
 8)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDGS.
  
 9)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON ELECTRICAL PLANS.
  
 PLEASE NOTE: UPON SUBMITTALS OF
 GENERATOR SPECS ETC, THERE MAY BE OTHER
 COMMENTS TO FOLLOW.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]