| 2004-11-22 00:00:00 | ******* UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SEE 210.52C1 FOR RECEPT |
| | SPACING ALONG KITCHEN COUNTERSPACE. |
| | |
| | 2)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU. PLEASE ALSO SEE 310.16 FOR |
| | SIZING OF CONDUCTORS. |
| | |
| | 3)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS. |
| | |
| | 4)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDITIONS TO EXSITNG DWELLINGS. |
| | PLEASE PROVIDE LAYOUT FOR NEW AND OR |
| | EXISTINGTO MEET 2002 NEC FOR GFI'S AND |
| | SD'S. |
| | |
| | |
| | 5) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | |
| | 6)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | THIS IS A COMMON TEXT NOTE AND PLANS MAY |
| | NOT NEED TO MEET ALL OF THE ABOVE. |
| | |
| | 7)NOTE: PLEASE SUBMIT COMPLETE SPEC |
| | SHEETS ON NEW PROPOSED GENERATOR |
| | SYSTEM. |
| | PLEASE BE AWARE WE ARE CURRENTLY HAVING |
| | SOME ISSUES W/CERTAIN "MANUFACTURED" |
| | PRE-WIRED SYSTEMS THAT DO NOT MEET CODE |
| | COMPLIANCE. |
| | |
| | 8)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED BLDGS. |
| | |
| | 9)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | ON ELECTRICAL PLANS. |
| | |
| | PLEASE NOTE: UPON SUBMITTALS OF |
| | GENERATOR SPECS ETC, THERE MAY BE OTHER |
| | COMMENTS TO FOLLOW. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |