| 2004-11-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) SHT 12 SANITARY RISER DIAGRAM DOES |
| | NOT MEET CODE REQUIREMENTS. KITCHEN SINK |
| | IS NOT VENTED AND AS SHOWN IS AN "S" |
| | TRAP. SECTION 1002.3(5). AN AIR |
| | ADMITTENCE VALVE MAY BE USED UNDER THE |
| | COUNTER OF THE SINK PER SECTION 917, OR |
| | THE SINK MAY BE CONNECTED ON THE |
| | VERTICAL RISE OF THE VENT STACK AND |
| | ROUTED THROUGH THE WALL TO THE SINK. |
| | 2) THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS PERMIT REQUIRED. |
| | A. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. - |
| | PLANS INDICATE "ALL UNDERGROUND PIPE |
| | WILL BE GALVANIZED" PLEASE INDICATE WHAT |
| | TYPE OF PIPING WILL BE USED FOR THE REST |
| | OF THE PIPING. |
| | 3) PIPE SIZING NOT CORRECT PER TABLE |
| | 402(2). SEE RED LINE CORRECTIONS MADE ON |
| | ONE SET OF PLANS FOR CORRECT PIPE SIZE |
| | REQUIRED. |
| | 4) SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. - (DRYER ROOM) |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |