Plan Review Notes
Plan Review Notes For Permit 04101019
Permit Number 04101019
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT 12 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. KITCHEN SINK
 IS NOT VENTED AND AS SHOWN IS AN "S"
 TRAP. SECTION 1002.3(5). AN AIR
 ADMITTENCE VALVE MAY BE USED UNDER THE
 COUNTER OF THE SINK PER SECTION 917, OR
 THE SINK MAY BE CONNECTED ON THE
 VERTICAL RISE OF THE VENT STACK AND
 ROUTED THROUGH THE WALL TO THE SINK.
 2) THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT REQUIRED.
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -
 PLANS INDICATE "ALL UNDERGROUND PIPE
 WILL BE GALVANIZED" PLEASE INDICATE WHAT
 TYPE OF PIPING WILL BE USED FOR THE REST
 OF THE PIPING.
 3) PIPE SIZING NOT CORRECT PER TABLE
 402(2). SEE RED LINE CORRECTIONS MADE ON
 ONE SET OF PLANS FOR CORRECT PIPE SIZE
 REQUIRED.
 4) SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. - (DRYER ROOM)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692