| Notes |
| Date |
Text |
| 2004-11-09 00:00:00 | | | | PLEASE CORRECT THE FOLLOWING FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} MAIN BLDG TEMP #2 IS LISTED AS 3#3AL | | | WITH A 400 AMP OCP, SEE 310.16 (TABLE) | | | THE RISER SHOWS 4-3/0 AL. PLEASE | | | CORRELATE RISER AND PANELSCHEDULE | | | CONDUCTOR, OCP, AND CONDUIT SIZES. | | | | | | 2} PLEASE NOTE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER IS REQUIRED ON THE | | | TITLE BLOCK PER 61G15-23.002 FAC. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|