| Date |
Text |
| 2006-03-22 00:00:00 | ********* UNSAT ********** |
| | |
| | *** PLEASE SEE CHANGES IN PLANS FROM |
| | PREVIOUS WHICH HAD CREATE SOME COMMENTS. |
| | |
| | 1)NOTE: PLEASE SEE MISSING COUNTER SPACE |
| | GFI AS REQUIRED PER 210.52C1, THIS WAS |
| | ON PREVIOUS PLANS.' |
| | |
| | 2) NOTE: PLEASE SEE MISSING ISLAND |
| | RECEPT PER 210.52C2 |
| | ( ON PRE-PLANS) |
| | |
| | 3)NOTE: PLEASE SEE PREVIOUS PLANS SHOWED |
| | "J-BOXES" FOR UC LIGHTING, HOWEVER THESE |
| | BOXES HAVE NOW BEEN REMOVED , YET THE |
| | CIRCUTIING FOR THESE ARE STILL BEING |
| | SHOWN. |
| | |
| | 4)NOTE: PLEASE DEFINE DINING AREA ON |
| | PLANS, PLEASE SEE NEW RECEPTS NOW ADDED |
| | WHICH ARE ON LIGHTING CIRCUIT. PLEASE |
| | SEE 210.52B1 WHICH REQUIRES RECEPTS IN |
| | DINING RMS, BREALFAST AREAS AND THE LIKE |
| | TO BE ON ONE OR MORE OF THE SMALL |
| | APPLIANCE BRANCH CIRCUITS. |
| | PLEASE SEE TWO AREAS WHICH ARE LABLED |
| | "DEN", PLEASE SEE AREA ADJACENT TO THE |
| | KITCHEN WILL BE CONSIDERED THE DINING |
| | AREA. |
| | SHALL BE #12, 20 |
| | |
| | 5)NOTE: PLEASE CLARIFY RISER AS, PLANS |
| | ONLY ONE ONE METER/PANEL IN THE SAME |
| | LOCATION, HOWEVER PLEASE SEE RISER SHOWS |
| | THE METER/MAIN AND A SEPARATE PANEL WITH |
| | A MCB?? ARE THESE TWO PANEL? |
| | PLEASE ALSO SEE MIN CLEARENCE IS NOTED, |
| | HOWEVER IF CLEARENCE IS MET FOR |
| | METER/MAIN AND PANEL, THEN DISCONNECTING |
| | MEANS FOR CU IS NOT MET. PLEASE REVISE |
| | PLANS AND SHOW THE LAYOUT TO SCALE. |
| | PLEASE SEE NOTING THE TECHNICAL |
| | REQUIRMENT IS NOT ACCEPTABLE AS THERE |
| | SEEMS TO BE AN ISSUE WITH CLEARENCE IN |
| | THE FIELD. |
| | FBC 104.2.1, NEC 110.26 |
| | |
| | 6) NOTE: PLEASE SEE AN AHU WITH A |
| | DISCONNECT AND OCP IS NOW ADDED TO |
| | CLOSET WHICH IS NOT PERMITTED PER |
| | 110.26,240.24 |
| | PLEASE ALSO CORRELATE AS THIS DISC IS |
| | SHOWN AS 50A AND PANEL SEEMS TO INDICATE |
| | THE OCP AS 60A. PLEASE SEE 424.3VB WHICH |
| | REQUIRES A MIN OF 125% OCP.(THIS WOULD |
| | BE 60A MIN FOR 10KW). |
| | |
| | 7) NOTE: PLEASE SEE PANEL SCHEDULE |
| | MENTIONS NEW PACKAGE UNIT A/C , HOWEVER |
| | PLEASE SEE ELECTRICAL PLANS DO NOT SHOW |
| | THIS? |
| | PLEASE SHOW AND SHOW DISC'S AS REQUIRED |
| | PER 440.11 |
| | |
| | 8)NOTE: PLEASE SEE MISSING RECEPT FOR 2' |
| | OR MORE OF WALL SPACE PER 210.52 IN |
| | BEDRM. |
| | THIS IS REDLINED ON PLANS. |
| | |
| | 9) NOTE: PLEASE VERIFY NUMEROUS CIRCUITS |
| | ON PLANS WHICH SHOWS #12,HOWEVER |
| | INDICATES 15A OPC>? |
| | THIS IS ONLY A NOTE AS THIS DOES NOT |
| | VIOLATE CODE. PLEASE VERIFY,IF THIS IS |
| | SHOWN ON PLANS THIS WAY, THEN THIS IS |
| | WHAT IS REQUIRED TO BE INSTALLED. |
| | |
| | ** PLEASE VERIFY THE #3 AS EXISTING GEC, |
| | AS 250.66 REQUIRES A MIN OF #2. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |