Plan Review Notes
Plan Review Notes For Permit 04101013
Permit Number 04101013
Review Stop E
Sequence Number 6
Notes
Date Text
2006-03-22 00:00:00********* UNSAT **********
  
 *** PLEASE SEE CHANGES IN PLANS FROM
 PREVIOUS WHICH HAD CREATE SOME COMMENTS.
  
 1)NOTE: PLEASE SEE MISSING COUNTER SPACE
 GFI AS REQUIRED PER 210.52C1, THIS WAS
 ON PREVIOUS PLANS.'
  
 2) NOTE: PLEASE SEE MISSING ISLAND
 RECEPT PER 210.52C2
 ( ON PRE-PLANS)
  
 3)NOTE: PLEASE SEE PREVIOUS PLANS SHOWED
 "J-BOXES" FOR UC LIGHTING, HOWEVER THESE
 BOXES HAVE NOW BEEN REMOVED , YET THE
 CIRCUTIING FOR THESE ARE STILL BEING
 SHOWN.
  
 4)NOTE: PLEASE DEFINE DINING AREA ON
 PLANS, PLEASE SEE NEW RECEPTS NOW ADDED
 WHICH ARE ON LIGHTING CIRCUIT. PLEASE
 SEE 210.52B1 WHICH REQUIRES RECEPTS IN
 DINING RMS, BREALFAST AREAS AND THE LIKE
 TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE BRANCH CIRCUITS.
 PLEASE SEE TWO AREAS WHICH ARE LABLED
 "DEN", PLEASE SEE AREA ADJACENT TO THE
 KITCHEN WILL BE CONSIDERED THE DINING
 AREA.
 SHALL BE #12, 20
  
 5)NOTE: PLEASE CLARIFY RISER AS, PLANS
 ONLY ONE ONE METER/PANEL IN THE SAME
 LOCATION, HOWEVER PLEASE SEE RISER SHOWS
 THE METER/MAIN AND A SEPARATE PANEL WITH
 A MCB?? ARE THESE TWO PANEL?
 PLEASE ALSO SEE MIN CLEARENCE IS NOTED,
 HOWEVER IF CLEARENCE IS MET FOR
 METER/MAIN AND PANEL, THEN DISCONNECTING
 MEANS FOR CU IS NOT MET. PLEASE REVISE
 PLANS AND SHOW THE LAYOUT TO SCALE.
 PLEASE SEE NOTING THE TECHNICAL
 REQUIRMENT IS NOT ACCEPTABLE AS THERE
 SEEMS TO BE AN ISSUE WITH CLEARENCE IN
 THE FIELD.
 FBC 104.2.1, NEC 110.26
  
 6) NOTE: PLEASE SEE AN AHU WITH A
 DISCONNECT AND OCP IS NOW ADDED TO
 CLOSET WHICH IS NOT PERMITTED PER
 110.26,240.24
 PLEASE ALSO CORRELATE AS THIS DISC IS
 SHOWN AS 50A AND PANEL SEEMS TO INDICATE
 THE OCP AS 60A. PLEASE SEE 424.3VB WHICH
 REQUIRES A MIN OF 125% OCP.(THIS WOULD
 BE 60A MIN FOR 10KW).
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE
 MENTIONS NEW PACKAGE UNIT A/C , HOWEVER
 PLEASE SEE ELECTRICAL PLANS DO NOT SHOW
 THIS?
 PLEASE SHOW AND SHOW DISC'S AS REQUIRED
 PER 440.11
  
 8)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OR MORE OF WALL SPACE PER 210.52 IN
 BEDRM.
 THIS IS REDLINED ON PLANS.
  
 9) NOTE: PLEASE VERIFY NUMEROUS CIRCUITS
 ON PLANS WHICH SHOWS #12,HOWEVER
 INDICATES 15A OPC>?
 THIS IS ONLY A NOTE AS THIS DOES NOT
 VIOLATE CODE. PLEASE VERIFY,IF THIS IS
 SHOWN ON PLANS THIS WAY, THEN THIS IS
 WHAT IS REQUIRED TO BE INSTALLED.
  
 ** PLEASE VERIFY THE #3 AS EXISTING GEC,
 AS 250.66 REQUIRES A MIN OF #2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]