| Plan Review Notes For Permit 04101013 |
| Permit Number |
04101013 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-03-24 00:00:00 | ****DENIED**** | | | REFERENCE: FBC-2004 PLUMBING | | | | | | PLEASE ADJUST YOUR DRAWINGS TO REFLECT | | | THE FOLLOWING CHANGES REQUIRED FOR PLAN | | | REVIEW: | | | | | | 1. SHEET P-1 INDICATES A TANKLESS WATER | | | INSTANT HOT HEATER, MODEL TKJM 140,000 | | | BTU. THE P&T FOR TANKLESS HEATER SHOWN | | | IN WRONG LOCATION FOR NEW HEATER | | | LOCATION. PLEASE ADJUST DRAWING. | | | 2. SUBMIT SHEET P-2 WITH NEW TANKLESS | | | WATER HEATER ON WATER ISOMETRIC AND | | | REMOVE EXISTING 60 GALLON GAS FIRED | | | HEATER FROM ISOMETRIC. | | | 3. REMOVE GAS PIPE FROM SHEETS P-1 AND | | | P-2, PLUMBING CONTRACTOR TO SUBMIT | | | SEPERATE AS BUILTS UNDER GAS PERMIT. | | | 4. ADDED NEW CW SHOWER ON SHEET P-1 | | | NEEDS TO BE ADDED TO P-2 WATER | | | ISOMETRICS, ALSO INDICATE WHAT THE ITEM | | | IS NEXT TO SHOWER AND INDICATE THIS ITEM | | | ON WATER ISOMETRIC. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|