| Notes |
| Date |
Text |
| 2006-03-22 00:00:00 | *** DENIED *** | | | 1) MECHANICAL PLANS ARE SEALED BY AN | | | ENGINEER AND REQUIRES THE ENGINEER'S | | | INFORMATION PRINTED IN THE TITLE BLOCK, | | | PER FAC 61G15.23.002 . | | | | | | 2) PLEASE PROVIDE AN A/C EQUIPMENT LIST | | | ON THE MECHANICAL PLAN SHOW ALL | | | EQUIPMENT NEW AND EXISTING. | | | | | | 3) PLEASE SHOW LOCATION OF CONDENSER | | | UNITS ON MECHANICAL PLAN. | | | | | | 4) PLEASE PROVIDE COMBUSTION AIR AND | | | CALCULATIONS FOR GAS CLOTHES DRYER AND | | | GAS INSTA-HOT WATER HEATER ON MECH. | | | PLANS. | | | | | | 5) REVISED MECHANICAL AND ELECTRICAL | | | PLANS SUBMITTED, SECOND FLOOR PLAN DO | | | NOT MATCH PLEASE CORRECT. | | | | | | 6) ELECTRICAL PLANS ARE SHOWING 3 A/C | | | SYSTEMS, MECH. PLANS ONLY TWO PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|