| Date |
Text |
| 2005-03-02 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) FROM PREVIOUS REVIEW: |
| | |
| | 2) SHT P-2 SANITARY RISER DIAGRAM, AT |
| | THE WASH MACHINE, THE CLEANOUT SHALL BE |
| | LOCATED 4 FEET ABOVE THE FLOOR FOR |
| | ACCESS OR SHALL LOOK OUT TO THE |
| | EXTERIOR OF THE WALL. SECTION 708.10 |
| | 4) SHT P-2 GAS ISOMETRIC SHOWS NEW |
| | LOCATION OF GAS METER, BUT UPSTREAM OF |
| | THE METER IS THE GAS GRILL (30K BTU). |
| | THIS APPLIANCE SHALL BE SHOWN |
| | DOWNSTREAM OF THE METER/REGULATOR. |
| | 5) THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - ALL CUT SECTION LENGTHS |
| | ARE NOT SHOWN ON ISOMETRIC. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). - INDICATE TABLE/TABLES USED. - |
| | TOTAL BTU LOAD IS NOT SHOWN AND THE |
| | TABLES USED ARE NOT SHOWN. |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM |
| | PER FBC-2001 FUEL GAS CODE APPENDIX A - |
| | USE OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. - FOR DRYER ROOM |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY |
| | LINES THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, |
| | BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE |
| | OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK |
| | AND APPURTENANCES PER NFPA 58. IF THE |
| | TANK IS BELOW GROUND THE CONTAINER SHALL |
| | BE SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 6) ENGINEERS SHALL LEGIBLY INDICATE THE |
| | NAME, ADDRESS, AND LICENSE NUMBER ON |
| | EACH SHEET. IF PRACTICING THROUGH A |
| | DULY AUTHORIZED ENGINEERING BUSINESS THE |
| | ENGINEER SHALL AS WELL AS INDICATE THE |
| | NAME, ADDRESS, AND CERTIFICATE OF |
| | AUTHROIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FS 471.025 |
| | 7) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME PER FAC 61G15-23.002(1) & FS |
| | 471.025. PER FBPE INITIALS ARE NOT |
| | ACCEPTABLE. IF THIS IS YOUR LEGAL |
| | SIGNATURE, A SIGNED/SEALED/DATED |
| | NOTORIZED LETTER INDICATING YOUR LEGAL |
| | SIGNATURE IS REQUIRED FOR OUR FILES. |
| | 8) PER ZONING NOTE THE GARAGE WILL NOT |
| | BE BUILT. PLEASE INDICATE WHERE THE |
| | WATER HEATER WILL BE LOCATED. INDICATE |
| | IF THE WATER HEATER WILL BE RATED FOR |
| | OUTSIDE USE OR IF IT WILL BE LOCATED |
| | INSIDE. SECTION 104.2.1 |
| | *************NEW COMMENT*********** |
| | 1B) ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUP SHALL CONNECT THE THE |
| | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT. THE W/M |
| | SHALL CONNECT DOWNSTREAM OF THE TOILET |
| | AND LAV OF THE POWDER ROOM . |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |