Plan Review Notes
Plan Review Notes For Permit 04101013
Permit Number 04101013
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-28 00:00:00************* UNSAT ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW TAKEN DIRECTLY
 INSERTED FROM PREVIOUS REVIEW.
  
 1)NOTE: OK.
  
  
 2)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS AND REMODEL OF EXISTING
 DWELLINGS.
 PLEASE SHOW LAYOUT FOR ALL REQUIRED
 SD'S
 PER NFPA-72 8-1.4.1.6.2
 SMOKE DETECTORS ARE REQUIRED INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. ON EACH
 LEVEL OF A MULTI-LEVEL DWELLING UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.2
 **
 PLEASE ALSO SHOW LAYOUT FOR ALL RECEPTS,
 NEW OR EXISTING WHICH ARE REQUIRED TO BE
 GFI PROTECTED. 210.8
 PLEASE SEE FBC 3401.7.1.2.1 FOR
 ADDITIONS, AND 3401.7.2.6 FOR OVER 50%.
  
 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 4)NOTE: OK.PLEASE SEE CLEARENCE FOR
 110.26 FOR ELECTRICAL EQUIPMENT.
  
  
 5)NOTE: PLEASE HAVE ALL INFORMATION ON
 TITLE BLOCK BE CLEAR AND VISABLE.
 PLEASE SEE BELOEW FOR REQUIRED CA #.
 PLEASE SEE FAC 61G15-23.002, FS 471.023
 PLEASE ALSO SEE FS 471.025 WHICH
 REQUIRES LEGAL SIGNATURE FOR SIGNED AND
 SEALED PLANS. PLANS SEEM TO BE INITIALED
 WHICH ARE NOT ACCEPTABLE. IF PLANS ARE
 INDEED SIGNED WITH LEGAL SIGNATURE,
 PLEASE PROVIDE AND SIGNED,SEALED,
 NOTORIZED LETTER FOR LEGAL SIGNATURE.
 THIS WILL BE PLACED IN SIGNATURE FILE
 AND CAN BE USED FOR FUTURE REFERENCE.
  
 6)NOTE: PLEASE SHOW NEW FOOTER STEEL TO
 BE PART OF GROUNDING ELECTRODE SYSTEM.
 250.50
  
 *** NEW NOTES ***
  
 1)NOTE: PLEASE SEE PLANS MENTIONS NEW
 PANEL "A" AND EXISTING PANEL.?? PLEASE
 CLARIFY.
  
 2)NOTE: PLEASE SEE ATTACHED FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS, PLEASE SEE NOTICE ONLY
 GIVEN AT THIS TIME.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS. (ZONING ETC).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW