| 2004-11-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT P-2 SANITARY RISER DIAGRAM, AT |
| | THE WASH MACHINE, DOUBLE SANITARY TEE |
| | PATTERNS SHALL NOT RECEIVE THE |
| | DISCHARGE |
| | OF APPLIANCES WITH PUMPING ACTION |
| | DISCHARGE. SECTION 706.3. THE WASH |
| | MACHINE SHALL CONNECT BELOW THE LAUNDRY |
| | SINK. |
| | 2) SHT P-2 SANITARY RISER DIAGRAM, AT |
| | THE WASH MACHINE, THE CLEANOUT SHALL BE |
| | LOCATED 4 FEET ABOVE THE FLOOR FOR |
| | ACCESS OR SHALL LOOK OUT TO THE |
| | EXTERIOR |
| | OF THE WALL. SECTION 708.10 |
| | 3) SHT P-2 WATER RISER DIAGRAM, AT THE |
| | WASH MACHINE, WATER HAMMER ARRESTORS |
| | ARE |
| | REQUIRED PER SECTION 604.9 AND SHALL BE |
| | LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING. |
| | PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | 4) SHT P-2 GAS ISOMETRIC SHOWS NEW |
| | LOCATION OF GAS METER, BUT UPSTREAM OF |
| | THE METER IS THE GAS GRILL (30K BTU). |
| | THIS APPLIANCE SHALL BE SHOWN |
| | DOWNSTREAM |
| | OF THE METER/REGULATOR. |
| | 5) THE FOLLOWING INFORMATION IS |
| | REQUIRED |
| | FOR GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). - INDICATE TABLE/TABLES USED |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM |
| | PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. - FOR DRYER ROOM |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY |
| | LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, |
| | BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK |
| | AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 6) ENGINEERS SHALL LEGIBLY INDICATE THE |
| | NAME, ADDRESS, AND LICENSE NUMBER ON |
| | EACH SHEET. IF PRACTICING THROUGH A |
| | DULY |
| | AUTHORIZED ENGINEERING BUSINESS THE |
| | ENGINEER SHALL AS WELL AS INDICATE THE |
| | NAME, ADDRESS, AND CERTIFICATE OF |
| | AUTHROIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FS 471.025 |
| | 7) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME PER FAC 61G15-23.002(1) & FS |
| | 471.025. PER FBPE INITIALS ARE NOT |
| | ACCEPTABLE. IF THIS IS YOUR LEGAL |
| | SIGNATURE, A SIGNED/SEALED/DATED |
| | NOTORIZED LETTER INDICATING YOUR LEGAL |
| | SIGNATURE IS REQUIRED FOR OUR FILES. |
| | 8) PER ZONING NOTE THE GARAGE WILL NOT |
| | BE BUILT. PLEASE INDICATE WHERE THE |
| | WATER HEATER WILL BE LOCATED. INDICATE |
| | IF THE WATER HEATER WILL BE RATED FOR |
| | OUTSIDE USE OR IF IT WILL BE LOCATED |
| | INSIDE. SECTION 104.2.1 |
| | |
| | |