Plan Review Notes
Plan Review Notes For Permit 04101013
Permit Number 04101013
Review Stop M
Sequence Number 1
Notes
Date Text
2004-11-30 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES THE AHU IN
 THE LAUNDRY ROOM WITH THE GAS DRYER.
 PLEASE CLARIFY RETURN AIR DUCT
 LOCATION.
 PER 2001 FBC(M) 303.2, APPLIANCES SHALL
 NOT BE LOCATED IN HAZARDOUS AREAS
 UNLESS
 LISTED AND APPROVED FOR THE SPECIFIC
 INSTALLATION.PLEASE PROVIDE DETAIL OF
 THE DUCT SYSTEM FOR AHU #2.GAS
 CONTAMINANT SHALL NOT BE RE-CIRCULATED.
 SHOW COMPLIANCE WITH 2001 FBC(M) 303.3.
  
 2.PROVIDE MANUFACTURERS
 SUBMITTAL/INSTALLATION INSTURCTIONS FOR
 THE GAS DRYER.
  
 3.PER 2001 FBC(M)601.4 RETURN AIR IS
 TO BE EQUAL TO THE SUPPLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.