| Plan Review Notes For Permit 04101013 |
| Permit Number |
04101013 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-30 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 INDICATES THE AHU IN | | | THE LAUNDRY ROOM WITH THE GAS DRYER. | | | PLEASE CLARIFY RETURN AIR DUCT | | | LOCATION. | | | PER 2001 FBC(M) 303.2, APPLIANCES SHALL | | | NOT BE LOCATED IN HAZARDOUS AREAS | | | UNLESS | | | LISTED AND APPROVED FOR THE SPECIFIC | | | INSTALLATION.PLEASE PROVIDE DETAIL OF | | | THE DUCT SYSTEM FOR AHU #2.GAS | | | CONTAMINANT SHALL NOT BE RE-CIRCULATED. | | | SHOW COMPLIANCE WITH 2001 FBC(M) 303.3. | | | | | | 2.PROVIDE MANUFACTURERS | | | SUBMITTAL/INSTALLATION INSTURCTIONS FOR | | | THE GAS DRYER. | | | | | | 3.PER 2001 FBC(M)601.4 RETURN AIR IS | | | TO BE EQUAL TO THE SUPPLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|