Plan Review Notes
Plan Review Notes For Permit 04100990
Permit Number 04100990
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-02 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED,DATED AND SEALED AN ENGINEER
 PER FS 471.003H(3)
  
 2)NOTE:PLEASE INCLUDE AN MEANS OF
 DISCONNECT FROM EM/PWR RECEPT INTO BLDG.
 PER 225.31,DISC GROUPED PER 230.72, DISC
 PER 230.76,230.79
  
 3)NOTE: PLEASE SEE POSSIBLE FIRE/BLDG
 REVIEWCOMMENTS. PLANS APPEAR TO SHOW
 CONDUITS BEING ROUTED IN STAIRWAY?
  
 4)NOTE: PLEASE SEE FS 481.221/471.025
 ALL SEALS ARE TO BE CLEAR AND VISABLE
 WITH ALL REQUIRED INFORMATION.
 SEAL(S) IS NOT CLEAR ON ALL SHEETS.
 PLEASE BE SURE NEW SEAL FOR ENGINEER IS
 ALSO VISABLE.
  
 5)NOTE: PLEASE VERIFY ADDRESS SHOWN ON
 TITLE BLOCK. NAMES OKEE SQUARE, WHICH IS
 ON OKEECHOBEE BLVD? YET, JOB APPL/PLANS
 SHOWS A BANYAN BLVD ADDRESS?? APPEARS TO
 BE CHANNEL 5 SITE??
  
  
 6)NOTE: PLAN NOTES MENTIONS, LOAD STUDY
 TO BE DONE OVER A 30 DAYS. LOAD ON
 EXISTING SERVICE SHOULD BE AVAILABLE DUE
 TO BLDG BEING COMPLETED IN THE LAST
 COUPLE OF YEARS. THIS IS REQUIRED AT
 THIS TIME. IF LOAD STUDY CAN BE DONE AT
 THIS TIME BEFORE PERMIT IS ISSUED. THIS
 IS ACCEPTABLE ALSO.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE NA AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]