| Plan Review Notes For Permit 04100990 |
| Permit Number |
04100990 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)SOME SHEETS ON THE CALCS REFER TO | | | IBC RATHER THAN FBC. | | | | | | 2.)DECLARE A BUILDING TYPE, OCCUPANCY | | | OF NEW SPACE, OCCUPANCY OF SPACE | | | ADJACENT AND BELOW. | | | | | | 3.)CLEARLY INDICATE FIRE SEPARATION | | | BETWEEN OCCUPANCIES.THE RATING FOR | | | THE | | | FLOOR/CEILING ASSEMBLY IS NOT GIVEN. | | | PROVIDE ASSEMBLY NUMBER | | | OR CALCULATED FIRE RESISTANCE IF | | | REQUIRED. | | | | | | 4.)THE DETAILS DO NOT CORRELATE WITH | | | THE FLOOR PLAN.THE DETAIL FOR U419 | | | DOES NOT PROVIDE WHICH RATING YOU ARE | | | USING; DOES NOT CORRELATE WITH THE | | | FLOOR | | | PLAN.FLOOR PLAN INDICATES A 2 HR WALL | | | BUT DOES NOT REFER TO U419 OR DETAIL. | | | | | | 5.)SHEET E2 APPEARS TO HAVE CONDUIT | | | PENETRATING A STAIRWAY ASSEMBLY WHICH | | | IS | | | NOT ALLOWED FBC1006.1.3.1. | | | | | | 6.)IS THE MEZZANINE AREA TO BE | | | SPRINKLED?NO SPRINKLER HEADS ARE SHOWN | | | IN THIS AREA. |
|