| Plan Review Notes For Permit 04100928 |
| Permit Number |
04100928 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | FROM PREVIOUS REVIEW: | | | 2) SUBMIT CALCULATIONS FOR PRIMARY ROOF | | | DRAINS. SHOW SQUARE FEET AREA OF ROOF | | | AND 1/2 AREA OF ALL VERTICAL WALLS | | | INCLUDING PARAPETS ADDED TO THE AREA OF | | | THE ROOF. SHOW THE AREA OF ROOF DRAINED | | | AT EACH DOWNSPOUT. INDICATE THE SLOPE | | | OF | | | THE GUTTER PER TABLE 1106.6. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|