2005-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEW:
 2) SUBMIT CALCULATIONS FOR PRIMARY ROOF
 DRAINS. SHOW SQUARE FEET AREA OF ROOF
 AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE AREA OF
 THE ROOF. SHOW THE AREA OF ROOF DRAINED
 AT EACH DOWNSPOUT. INDICATE THE SLOPE
 OF
 THE GUTTER PER TABLE 1106.6.
  
  