Plan Review Notes
Plan Review Notes For Permit 04100928
Permit Number 04100928
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-09 00:00:00DENIED
 REFERNEC: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A SERVICE SINK ARE REQUIREDL.
  
 2) SUBMIT A ROOF DETAIL. SHOW PRIMARY
 AND SECONDARY ROOF DRAINS. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FEET AREA OF
 ROOF AND 1/2 AREA OF ALL VERTICAL WALLS
 ADDED TO THE AREA OF THE ROOF. SHOW ALL
 PIPE SIZES OF ROOF LEADERS AND/OR
 GUTTERS AND DOWNSPOUTS. IF GUTTERS AND
 DOWNSPOUTS SHOW SIZE OF EACH AND SHOW
 SLOPE OF GUTTER ALONG WITH THE HIGH
 POINTS OF GUTTERS PER TABLE 1106.6
  
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]