| 2004-10-26 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS SHOW A NEW BATH |
| | , YET NO CIRCUITING IS SHOWN FOR THIS?? |
| | |
| | 2)NOTE: PLEASE SEE 250.6,250.24. |
| | EQUIPMENT GROUNDING CONDUCTORS ARE NOT |
| | PERMITTED BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 3)NOTE: PLEASE SIZE GROUDING ELECTRODE |
| | CONDUCTOR PER 250.66. SHOWN AS #3?? |
| | PLEASE SEE THAT SEC'S ARE PARALLEL 3/0'S |
| | |
| | 4)NOTE: PLEASE SEE LS 101 5-8 FOR MIN |
| | LT REQUIRED IN SPACE. |
| | |
| | 5)NOTE: PLEASE SEE ADDRESS SHOWN ON PLAN |
| | -S AND SPPLICATION IS SHOWN AS 1710 "OLD |
| | " OKEECHOBEE. THIS IS OKEECHOBEE RD. AND |
| | NOT OLD OKEE. PLEASE ALSO SEE BLDG |
| | REVIEW COMMENTS FOR THIS. |
| | ' |
| | ********** NOTE ********** |
| | THIS COMMENT FOR OTHER THAN ELECTRICAL |
| | SHEETS. |
| | PLEASE SEE ALL PLANS(LANSCAPE ETC) ARE |
| | REQUIRED TO BE SIGNED,DATED AND SEALED |
| | BY ALL ARCH'S ENGINEERS. SOME PLANS DO |
| | NOT CONTAIN ANY SEALS ETC. |
| | PLEASE ALSO SEE MISSING INFORMATION ON |
| | TITLE BLOCKS REQUIRED UNDER FAC 61G1-16- |
| | .004, FS 481.219 |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |