Plan Review Notes
Plan Review Notes For Permit 04100928
Permit Number 04100928
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-26 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS SHOW A NEW BATH
 , YET NO CIRCUITING IS SHOWN FOR THIS??
  
 2)NOTE: PLEASE SEE 250.6,250.24.
 EQUIPMENT GROUNDING CONDUCTORS ARE NOT
 PERMITTED BEFORE THE FIRST MEANS OF
 DISCONNECT.
  
 3)NOTE: PLEASE SIZE GROUDING ELECTRODE
 CONDUCTOR PER 250.66. SHOWN AS #3??
 PLEASE SEE THAT SEC'S ARE PARALLEL 3/0'S
  
 4)NOTE: PLEASE SEE LS 101 5-8 FOR MIN
 LT REQUIRED IN SPACE.
  
 5)NOTE: PLEASE SEE ADDRESS SHOWN ON PLAN
 -S AND SPPLICATION IS SHOWN AS 1710 "OLD
 " OKEECHOBEE. THIS IS OKEECHOBEE RD. AND
 NOT OLD OKEE. PLEASE ALSO SEE BLDG
 REVIEW COMMENTS FOR THIS.
 '
 ********** NOTE **********
 THIS COMMENT FOR OTHER THAN ELECTRICAL
 SHEETS.
 PLEASE SEE ALL PLANS(LANSCAPE ETC) ARE
 REQUIRED TO BE SIGNED,DATED AND SEALED
 BY ALL ARCH'S ENGINEERS. SOME PLANS DO
 NOT CONTAIN ANY SEALS ETC.
 PLEASE ALSO SEE MISSING INFORMATION ON
 TITLE BLOCKS REQUIRED UNDER FAC 61G1-16-
 .004, FS 481.219
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]