| 2004-11-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR THE SIZING OF THE GREASE |
| | INTERCEPTOR. WASTE ORD. #2938-96 (561) |
| | 837-4074. ATTACH COPY OF RESPONSE |
| | LETTER |
| | FROM MR. COMPO TO PLANS WHEN |
| | RESUBMITTING. |
| | 2) SHTS P1.01 AND P2.01 SAFE WASTE NOT |
| | APPROVED AT ICE MACHINE. FLOOR DRAIN |
| | NOT |
| | APPROVED FOR INDIRECT WASTE. SECTIONS |
| | 802.3 & 802.3.2. (ALSO DELETE SAFE |
| | WASTE |
| | DETAIL) |
| | 3) DISH WASHER SHALL NOT CONNECT TO |
| | GREASE SYSTEM. DISH WASHER SHALL |
| | CONNECT |
| | TO THE SANITARY SYSTEM. |
| | 4) SHTS P1.01 & P2.01 SHALL NOT DRAIN |
| | THROUGH THE HORIZONTAL WET VENT OF THE |
| | BATHROOM FIXTURES. SECTION 909.1. HAND |
| | SINK SHALL DISCHARGE DOWNSTREAM OF THE |
| | BATHROOM FIXTURES. |
| | 5) THE FOLLOWING INFORMATION IS |
| | REQUIRED |
| | FOR THE GAS PERMIT. SEPARATE GAS PERMIT |
| | REQUIRED. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. TYPE OF GAS, (LP OR NATURAL) |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM |
| | PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | F. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY |
| | LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, |
| | BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | G. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 6) SHOW CLEAR FLOOR SPACE AND TURNING |
| | AREA FOR EACH TOILET ROOM PER SECTIONS |
| | 11-4.16.2, 11-4.19.3, AND 11-4.22.3. |
| | 7) THE FIRM LICENSE NUMBER SHALL BE |
| | CONTAINED IN THE TITLE BLOCK PER FAC |
| | 61G1-16.004(2) & FS 481.219 |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |