Plan Review Notes
Plan Review Notes For Permit 04100921
Permit Number 04100921
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR THE SIZING OF THE GREASE
 INTERCEPTOR. WASTE ORD. #2938-96 (561)
 837-4074. ATTACH COPY OF RESPONSE
 LETTER
 FROM MR. COMPO TO PLANS WHEN
 RESUBMITTING.
 2) SHTS P1.01 AND P2.01 SAFE WASTE NOT
 APPROVED AT ICE MACHINE. FLOOR DRAIN
 NOT
 APPROVED FOR INDIRECT WASTE. SECTIONS
 802.3 & 802.3.2. (ALSO DELETE SAFE
 WASTE
 DETAIL)
 3) DISH WASHER SHALL NOT CONNECT TO
 GREASE SYSTEM. DISH WASHER SHALL
 CONNECT
 TO THE SANITARY SYSTEM.
 4) SHTS P1.01 & P2.01 SHALL NOT DRAIN
 THROUGH THE HORIZONTAL WET VENT OF THE
 BATHROOM FIXTURES. SECTION 909.1. HAND
 SINK SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES.
 5) THE FOLLOWING INFORMATION IS
 REQUIRED
 FOR THE GAS PERMIT. SEPARATE GAS PERMIT
 REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM
 PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY
 LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS,
 BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 6) SHOW CLEAR FLOOR SPACE AND TURNING
 AREA FOR EACH TOILET ROOM PER SECTIONS
 11-4.16.2, 11-4.19.3, AND 11-4.22.3.
 7) THE FIRM LICENSE NUMBER SHALL BE
 CONTAINED IN THE TITLE BLOCK PER FAC
 61G1-16.004(2) & FS 481.219
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]