| 2004-11-16 00:00:00 | DENIED: | | | 1.PLAN SHEET M2.01 CONDENSER MOUNTING | | | DETAIL - PLAN INDICATES 18" FROM THE | | | ROOF SURFACE TO THE BOTTOM OF THE | | | SUPPORT RAIL.THE 18" CLEARANCE IS | | | OKAY | | | IF THE WIDTH OF THE CONDENSER IS | | | GREATER | | | THAN 24" AND LESS THAN 36".SEE 2001 | | | FBC 1511.7 FOR PROPER CLEARANCE. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS PER 2001 | | | FBC(M)606.4.1. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPPRESSION, AND WALK-IN COOLERS. | | | PLEASE PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS, CUT SHEETS AND PLAN | | | SHOWING GREASE DUCT TERMINATION, LAYOUT, | | | CLEANOUTS, AND CLEARANCES TO | | | COMBUSTIBLES WITH THE PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @(561)805-6719. |
|