Plan Review Notes
Plan Review Notes For Permit 04100921
Permit Number 04100921
Review Stop M
Sequence Number 1
Notes
Date Text
2004-11-16 00:00:00DENIED:
 1.PLAN SHEET M2.01 CONDENSER MOUNTING
 DETAIL - PLAN INDICATES 18" FROM THE
 ROOF SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL.THE 18" CLEARANCE IS
 OKAY
 IF THE WIDTH OF THE CONDENSER IS
 GREATER
 THAN 24" AND LESS THAN 36".SEE 2001
 FBC 1511.7 FOR PROPER CLEARANCE.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER 2001
 FBC(M)606.4.1.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION, AND WALK-IN COOLERS.
 PLEASE PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS, CUT SHEETS AND PLAN
 SHOWING GREASE DUCT TERMINATION, LAYOUT,
 CLEANOUTS, AND CLEARANCES TO
 COMBUSTIBLES WITH THE PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @(561)805-6719.