| 2004-11-12 00:00:00 | 1) PANIC HARDWARE REQUIRED ON EXIT | | | DOORS SUBJECT TO AN OCCUPANCY OF | | | 100 OR MORE PERSONS. | | | | | | 2) HOW WILL EXITING BE MAINTAINED | | | IN THE REAR OF THE ESTABLISHMENT. | | | AREAS ARE NOTED AS STORAGE AREAS. | | | | | | 3) SEPARATE PLANS AND PERMITS | | | REQUIRED FOR ANY HOOD,DUCT, AND | | | SUPPRESSION SYSTEMS. | | | | | | 4) PLEASE PROVIDE DRAWING OF SIGN | | | PLANNED FOR THE FRONT DOOR INDICATING | | | DOOR TO REMAIN UNLOCKED DURING | | | BUSINESS HOURS. | | | | | | 5) PLEASE INDICATE INTERIOR FINSH | | | CLASSIFICATION FOR WALLS AND | | | CEILINGS. | | | | | | 6) IS THE BUILDING FIRE SPRINKLER | | | PROTECTED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|