Plan Review Notes
Plan Review Notes For Permit 04100921
Permit Number 04100921
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-29 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE ARCH'S TITLE BLOCK
 AND MISSING LICENSE INFOMATION REQUIRED
 PER FS 481.219 AND FAC 61G1-16.004.
  
 2)NOTE: PLEASE INCLUDE REQUIRED "SHOW"
 WINDOW RECEPTS. PER 210.62
 PLEASE ALSO SEE 220.12 FOR LOADING.
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE NOTE: ALL RECEPTS IN
 KITCHEN TO BE GFI/GFI PROTECTED.
 210.8
  
 5)NOTE: PLEASE PROVIDE NOTE FOR SHUT-
 DOWN OF ALL ELECTRICAL EQUIPMENT IN
 HOODS/EXHAUST ETC.
 PLEASE SEE NFPA-96
 CHAPTER 7
 CHAPTER 10
  
 6)NOTE: PLEASE PROVIDE LOAD ON THE EXIST
 -ING MDP SHOWN.
 215.5,220
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S) WHICHY MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]