2005-01-24 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY SCOPE OF WORK.
 PLANS APPEAR TO SHOW SOME NEW
 ELECTRICAL YET EXISTING IS NOT
 INDICATED?
 IF SCOPE OF WORK IS FOR NEW RE-WIRE DUE
 TO FIRE, PLEASE SUBMIT PLANS FOR
 COMPLATE LAYOUT OF ELECTRICAL DEVICES
 PER 2002 NEC AND NFPA-72 FOR SD'S.
 PLEASE SEE
 210.52,210.52C1,210.8A6,210.52D/210.11C3
 10.52,210.52C1,210.8A6,210.52D/210.11C3
 210.52E,210.63,440.11.
 PLEASE ALSO SEE 220.31 FOR LOAD
 CALCUALTIONS, AHU/HEAT SHOWN AT 40%
 DERATING??.
  
 2)NOTE: PLEASE SEE THIS PERMIT CAME IN
 FOR A $50,000 MISC PERMIT. AN MISC
 INSPECTION BY AN ELECTRICAL INSPECTOR
 MAY BE NEEDED TO DETERMINE COMPLETE
 SCOPE OF WORK.
 PLEASE ALSO SEE CHAPTER 34 FO THE FBC
 FOR REWORK OF EXISTING HOUSES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717