| Notes |
| Date |
Text |
| 2005-01-24 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE CLARIFY SCOPE OF WORK. | | | PLANS APPEAR TO SHOW SOME NEW | | | ELECTRICAL YET EXISTING IS NOT | | | INDICATED? | | | IF SCOPE OF WORK IS FOR NEW RE-WIRE DUE | | | TO FIRE, PLEASE SUBMIT PLANS FOR | | | COMPLATE LAYOUT OF ELECTRICAL DEVICES | | | PER 2002 NEC AND NFPA-72 FOR SD'S. | | | PLEASE SEE | | | 210.52,210.52C1,210.8A6,210.52D/210.11C3 | | | 10.52,210.52C1,210.8A6,210.52D/210.11C3 | | | 210.52E,210.63,440.11. | | | PLEASE ALSO SEE 220.31 FOR LOAD | | | CALCUALTIONS, AHU/HEAT SHOWN AT 40% | | | DERATING??. | | | | | | 2)NOTE: PLEASE SEE THIS PERMIT CAME IN | | | FOR A $50,000 MISC PERMIT. AN MISC | | | INSPECTION BY AN ELECTRICAL INSPECTOR | | | MAY BE NEEDED TO DETERMINE COMPLETE | | | SCOPE OF WORK. | | | PLEASE ALSO SEE CHAPTER 34 FO THE FBC | | | FOR REWORK OF EXISTING HOUSES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|