| Date |
Text |
| 2005-01-26 00:00:00 | 1. DOORS 132 FOR MECHANICAL ROOM 132 |
| | ARE NOT FIRE RATED BUT ARE LOCATED |
| | IN A RATED WALL. PLEASE REVISE PLANS |
| | TO REFLECT THAT THESE DOORS WILL BE |
| | FIRE RATED. |
| | |
| | 2. ALL FIRE RATED DOORS ARE TO BE |
| | EQUIPPED WITH LISTED AND APPROVED |
| | SELF-CLOSING DEVICES TO CAUSE THE |
| | DOORS TO POSITIVELY LATCH WHEN |
| | CLOSED. |
| | |
| | 3. SINCE THE BUILDING IS NEW, THE |
| | FIRE ALARM SYSTEM MUST BE MONITORED |
| | BY UL LISTED CENTRAL STATION APPROVED |
| | FOR CENTRAL STATION SERVICE. YOUR |
| | RESPONSE TO COMMENT # 19 IS NOT |
| | CORRECT AS THE EXISTING BUILDINGS |
| | THAT ARE PRESENTLY MONITORED ON THE |
| | CAMPUS DID NOT HAVE TO MEET THIS |
| | SPECIFIC REQUIREMENTS. PLEASE NOTE |
| | THIS. |
| | |
| | 4. PLEASE EXPLAIN TYPICAL CARD READER |
| | OUTLETS ON PAGE E1.9. HOW WILL CARD |
| | READERS BE USED AND WILL THEY POSE |
| | ANY PROBLEMS FOR EXITING. |
| | |
| | 5. MAG-LOCKS APPEAR TO BE NOTED ON |
| | DOORS MARKED AS EXITS BETWEEN ROOM 140 |
| | AND 142. PLEASE EXPLAIN USE OF LOCKS |
| | AND EXITING. |
| | |
| | 6. FIRE SPRINKLER PROTECTION WILL |
| | BE REQUIRED UNDERNEATH DUCTS THAT ARE |
| | OVER FOUR FEET WIDE. |
| | |
| | 7. THE STORAGE OF BASKETBALLS AND |
| | SHELVING CANNOT DAMAGE OR INTERFERE |
| | WITH THE FIRE ALARM EQUIPMENT |
| | LOCATED AT RECEPTION AREA. |
| | |
| | 8. IT APPEARS THAT ONLY SEVEN FIRE |
| | EXTINGUISHERS ARE PRESENT WITH ONE |
| | BEING LOCKED IN MECHANICAL ROOM # 166. |
| | ADDITIONAL FIRE EXTINGUISHERS APPEAR |
| | TO BE NEEDED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |