| 2004-11-12 00:00:00 | 1) DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH |
| | NFPA 241. |
| | |
| | 2) SUITABLE ROADS ARE REQUIRED FOR |
| | FIRE AND PARAMEDICAL ACCESS WHILE |
| | BUILDING IS UNDER CONSTRUCTION. |
| | |
| | 3) ELECTRONIC SWITCHES ARE |
| | REQUIRED ON FIRE LINE BACKFLOW |
| | DEVICE. |
| | |
| | 4) PLEASE ILLUSTRATE FIRE RESCUE |
| | STAGING LOCATIONS FOR FIRE |
| | APPARATUS. IT DOES NOT APPEAR THAT |
| | MANY LOCATIONS HAVE BEEN PROVIDED |
| | FOR FIRE RESCUE ACCESS. THE AREAS |
| | SEEN WOULD BE DIFFICULT TO TURN |
| | FIRE APPARATUS AROUND. |
| | |
| | 5) PLEASE INDICATE PROPOSED OCCUPANT |
| | LOADS FOR THE PROPOSED BUILDING. |
| | ALL ANCILLARY ROOMS TO THE GYM |
| | SHALL BE CALCULATED. |
| | |
| | 6) PLEASE PROVIDE FLAMESPREAD DATA |
| | ON GYMNASIUM DIVIDING CURTAIN. |
| | |
| | 7) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND |
| | CEILINGS. |
| | |
| | 8) TACTILE SIGNAGE REQUIRED AT |
| | ALL EXIT LOCATIONS. |
| | |
| | 9) SINCE THE BUILDING IS A MIXED |
| | OCCUPANCY, THE MOST STRINGENT OF |
| | THE OCCUPANCY TYPES WILL PREVAIL. |
| | |
| | 10) PLEASE EXPLAIN THE DESIGN TEAMS |
| | THEORY FOR THE MAIN INGRESS AND EGRESS |
| | FOR THE BUILDING. |
| | |
| | 11) MORE DETAILS REQUIRED ABOUT THE |
| | BLEACHERS. |
| | |
| | 12) ALL AUTMATIC SLIDERS USED FOR |
| | EXITING MUST MEET THE REQUIREMENTS FOR |
| | POWER OPERATED DOORS AND CONTAIN THE |
| | REQUIRED OPENING FEATURE WHEN LOSS |
| | OF POWER OCCURS. |
| | |
| | 13) PLEASE EXPLAIN UNDERCUT NOTE 3/8" |
| | FOR RATED FIRE DOORS. |
| | |
| | 14) PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE |
| | FOR FIRE RATED DOORS SHALL BE PRESENT |
| | ON EXIT DOORS SUBJECT TO AN OCCUPANCY |
| | OF 100 OR MORE PERSONS. |
| | |
| | 15) FIRE SPRINKLER HEADS SHALL NOT |
| | BE PAINTED WHEN CEILING AREAS ARE |
| | PAINTED. ANY FIRE SPRINKLER HEADS |
| | THAT ARE PAINTED SHALL BE REPLACED. |
| | |
| | 16) ANY SHAFT LARGE ENOUGH FOR PERSONS |
| | TO FALL INTO MUST BE MARKED "SHAFTWAY" |
| | WITH 6" HIGH LETTERS ON A CONTRASTING |
| | BACKGROUND. |
| | |
| | 17) BUILDING ADDRESS REQUIRED. A |
| | MINIMUM |
| | OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 18) PLEASE PROVIDE FLAMESPREAD RATINGS |
| | ON ACCOSTICAL PANELS. |
| | |
| | 19) FIRE ALARM SYSTEM SHALL BE |
| | MONITORED |
| | BY A UL LISTED FIRE ALARM COMPANY |
| | LISTED |
| | FOR CENTRAL STATION SERVICE. |
| | |
| | |
| | 20) PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 21) PLEASE EXPLAIN STEEL ACCESS |
| | LADDERS. |
| | WHAT IS THE RATIONALE BEING USED. |
| | |
| | 22) ON PAGE A10.1 AN AREA IS LABELED |
| | STORAGE 130 WHICH APPEARS TO BE |
| | INCORRECT. |
| | |
| | 23) SOME EXIT SIGNS APPEAR TO BE |
| | MISSING FROM SOME OF THE ELECTRICAL |
| | PAGES. |
| | |
| | 24) WHAT PREVENTS EMERGENCY LIGHTING |
| | AND EXIT SIGNS IN THE GYM FROM |
| | BEING DAMAGED. |
| | |
| | 25) WHAT WILL THE VOICE EVACUATION |
| | MESSAGE SAY FOR THE FIRE ALARM |
| | SYSTEM. |
| | |
| | 26) A NEW FIRE HYDRANT APPEARS |
| | TO BE LOCATED NEW THE NEW |
| | TRANSFORMERS BUT COULD NOT |
| | LOCATE A CALL-OUT FOR IT ON THE |
| | PLANS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |