| 2004-11-15 00:00:00 | ************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE 230.95, 240.13 FOR |
| | REQUIRED GFI PROTECTION OF MDP. |
| | |
| | 2)NOTE: PLEASE VERIFY/NOTE GROUNDING |
| | ATTACHEMENTS FOR TRANSFORMER ON RISER. |
| | WIRE AND CONDUIT SCHEDULE MENTIONS |
| | CONDUCTOR SIZE ONLY. |
| | 250.30 |
| | |
| | 3)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| | BE THE UTILITY OWNED TRANSFORMER ON |
| | RISER. IF FPL TRANSFORMER, THIS DOES NOT |
| | NEED TO BE SHOWN. |
| | THIS WORK WOULD BE DONE BY FPL AND NOT |
| | FALL UNDER NEC. |
| | NEC 90 |
| | |
| | 4)NOTE: PLEASE PROVIDE NOTE ON |
| | ELECTRICAL RISER SHEET E2.1 FOR |
| | REQUIREMENTS OF ELECTRICAL ROOM |
| | /DOORS/HARDWARE PER 110.26 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2004-11-05 00:00:00 | IN FOR ELECTRICAL REVIEW. |
| | ONE SET ONLY. |
| | **** NOTES TO FOLLOW WHEN REVIEW IS |
| | COMPLETE**** |
| | FULL REVIEW NOT DONE AT THIS TIME. |